Communication Cable
Please note the following communication cable installation requirements and suggestions:
• The remote SmartHub is designed for use with
shielded, twisted-pair, communication cable. Toro
recommends R7162D or equivalent.
• More than one cable run can be connected to the Surge
Protection Unit (SPU, part #35-7353).
• A remote SmartHub communication cable can emanate
from another remote SmartHub connection.
• If additional communication cable runs are installed for
future system expansion, each cable wire pair must be
terminated with a 600 ohm resistor (
Figure 15
).
• If the communication cable is routed in the same
trench as main power wires, or the SmartHub to
decoder module cables, a minimum of 12” (30.5cm)
separation is recommended to prevent voltage
induction on the communication cable. Check local
codes for actual requirements.
• Refer to the installation instructions provided with the
central control system for communication cable testing
procedures.
• If in-ground cable splices or repairs are required,
the connection must be properly insulated with a
waterproof splicing device. Using an appropriate
splicing kit, such as Scotchcast 82-A1 (or equivalent),
is recommended. Placing the cable splice in a small
valve box for protection and accessibility is a good
installation practice.
Steps:
1. Starting at the Surge Protection
Unit (SPU, part #35-7353), route
the communication (comm)
cable to each SmartHub leaving
enough cable at each location to
enable connection. See
Figure
12
.
If additional communication
cable is installed for future
system expansion, connect a
600 ohm resistor across the
wire pair at the end of the cable
as shown in
Figure 13
.
2. At the SmartHub, cut the
cable and pull both ends into the SmartHub
through the 3/4” (16mm) sweep conduit.
3. At the cable ends, strip the outer jacket and
inner insulation to expose the comm wires.
• SmartHub connection
: Attach a Phoenix
3-hole connector.
• SPU connection
: Attach a Phoenix 3-hole
connector.
• FIU connection
: Attach a RJ-11
connector.
4. For the SmartHub, plug comm line into the
modem port (
Figure 14)
.
Remove the modem wire connector(s) until
the comm cable has been tested. Refer
to the installation instructions provided with
the Central controller for testing
procedures.
Figure 13
600 Ohm
Resistor
Figure 12
SmartHub
SPU
See Note
18
Lynx® SmartHub Installation and User Guide
Figure 14