background image

Upgrade of Existing System,  

Using Existing Wiring

Communication Cable Type

Should be 2 or 3 copper conductors, solid or stranded, 

with PE pr PVC insulation, rated for at least 600V. For 

3-conductor cables, the third conductor will not be used 

and any exposed ends must be capped and sealed with an 

approved splice.

Communication Cable Length

The maximum wire run from the SmartHub to the farthest 

decoder is 6800’ (2072 meters) for 14 AWG (2.5mm

2

) cable. 

The total amount of  wire path is 14,000’ (4267 meters) for 

14 AWG (2.5mm

2

) cable.

Resistance

The maximum resistance of the wire path with the end 

shorted can be 37.7 Ohms. The minimum resistance of the 

wire path with the end open should be 1000 Ohms.

Noise

For the wire path to be tested, disconnect from the DIU (or 

other controller), connect an oscilloscope across the wire 

path, and power up the pump and any other equipment 

that would be running when watering. Measure the voltage 

across the open wire path. It should be less than 1 V p-p.

Short Circuits

After the GAC decoders are installed, measure the 

resistance across the two open wire path wires to insure 

that it is still greater than 1000 Ohms to insure that no 

shorts were introduced during the installation process.

Communication Cable to Power Cable Spacing

This recommendation applies to GAC communication 

installation. This minimum spacing to any power cable 

should be maintained to minimize the possibility of 

electrical interference which could affect the integrity of  

the GAC communication to decoders. If  there are power 

cables already installed running next to the communication 

cables that do not meet the minimum spacing, remdiation 

will be required to meet the minimum spacing listed in 

Table 2

 below.

Table 2

Power Cable Circuit 

Rating 

(Minimum KVA*)

Recommended Minimum 

Spacing**

0-3

6 inches (15 cm)

3-10

12 inches (30 cm)

10-20

24 inches (60 cm)

20-50

36 inches (90 cm)

50-100

48 inches (120 cm)

>100

60 inches (150 cm)

*Maximum voltage x current rating of circuit
**These are minimum spacing recommendations 

to minimize noise coupling. There may be greater 

separation required by safety agencies or local codes.

Decoder to Sprinkler Wires

Wire Type - Should be copper conductors, solid core, with 

PE or PVC insulation, rated for at least 600V

Wire Length

For 16 AWG or 1.5mm2  – Maximum length is 575 feet 

(175m)
For 18 AWG or 0.9mm2  – Maximum length is 400 feet 

(122m)

Decoder Module Installation

Remove an old decoder by cutting out the old splices. Make 

sure to cut the communication wires and station wires back 

to remove any green or corroded copper. Strip the wires 

and connect a new decoder module per Figure 4. All splices 

must be made with approved splice kits.

Valve Compatibility

Toro

Golf  VIH (Solenoid 89-1905 or 118-0248) 

at 150 PSI
400ft (122m) Max Solid Core, 18 AWG 

or 0.9mm2 Cable 2.3 Ohms/Conductor 

(400ft), 1 per Output
575ft (175m) Max Solid Core, 16 AWG 

or 1.5mm2 Cable 2.3 Ohms/Conductor 

(575ft), 2 per Output

Toro

252 Valve (Solenoid 102-1905 or 118-0248) 

at 150 PSI at AC Decoder, 1 per Output

Toro

220 Valve (Solenoid 102-0927) up to 220 

PSI (passing is 150 PSI) at AC Decoder,1 

per Output

Toro

216 Brass Valve (Solenoid 89-1673), Up 

to 220 PSI (passing is 150 PSI) at AC 

Decoder, 1 per Output

Rain Bird

Green Golf  VIH Solenoid at 150 PSI 

200ft Max Solid Core, 18 AWG or 0.9mm2 

Cable 1.2 Ohms/Conductor, 1 per Output 

328ft Max Solid Core, 16 AWG or 1.5mm2 

Cable 1.2 Ohms/Conductor, 2 per Output

Rain Bird

DV Solenoid (Black Wires) at 150 PSI at 

AC Decoder, 1 per Output

Rain Bird

PGA/PESB Solenoid (White Wires) at 150 

PSI at Decoder, 1 per Output

 

14

Lynx® SmartHub Installation and User Guide

Summary of Contents for Lynx SmartHub

Page 1: ...Lynx SmartHub for LSM GAC Installation and User Guide DEC and DAC Series...

Page 2: ...unication Cable 18 Communicating with the SmartHub 19 Layout 1 Local 19 Layout 2 Wired Lynx 20 Layout 3 Wireless 20 Radio Communication FIU to SmartHub 21 Changing the Frequency of the Radio 22 Operat...

Page 3: ...onduit of various diameters to enable power field ground and communication wiring to be routed into the pedestal for connection A mounting bolt positioner and basic mounting hardware components are in...

Page 4: ...n from direct sunlight rain wind and snow as possible IMPORTANT Do not mount the controller where it is exposed to direct spray from the irrigation system Steps 1 Drill two pilot holes 6 15 25cm apart...

Page 5: ...3 Strip the power cables and secure them to the terminal block Figure 3 Reference Table 1 for the appropriate type of power connection 4 Reinstall the power supply cover 5 Apply power to the controll...

Page 6: ...r 6 Pour concrete into the formed foundation hole Press the mounting bolt positioner into the concrete until it is flush and level with the foundation surface and aligned with the conduit 7 Finish the...

Page 7: ...lush with or below ground level and should be protected from damage using a valve box A 2 Measure the ground resistance per the instructions provided with the ground test instrument If reading is 10 o...

Page 8: ...x SmartHub Installation and User Guide 8 2 4m 8 2 4m 8 2 4m 8 2 4m 8 2 4m No solenoid power or communication cables within this zone pedestal or gateway concrete pad grounding rod grounding plate Figu...

Page 9: ...block Reference Table 1 and Figure 7 for the appropriate type of power connection 3 Reinstall the power supply cover 4 Apply power to the controller WARNING AC POWER WIRING MUST BE INSTALLED AND CONNE...

Page 10: ...without conduit All field wiring splices must be accessible to facilitate troubleshooting and or service Steps 1 Route communication cable from the controller to the station module installation locat...

Page 11: ...oubleshooting install wires with the same color code as the station wires Each station can activate up to two DC Latching Solenoids Out to additional modules Station Wires The Lynx SmartHub output boa...

Page 12: ...oute communication cable from the controller to the station decoder module installation location The maximum wire length between the controller and the decoder module is 6 800 2072 m 2 Secure the comm...

Page 13: ...on 3 s solenoid wires Station 4 Orange Wire Connect to one of Station 4 s solenoid wires Red Power Communication Wire Black Power Communication Wire Output Circuit 1 AC Solenoid Black Black Each stati...

Page 14: ...ng listed in Table 2 below Table 2 Power Cable Circuit Rating Minimum KVA Recommended Minimum Spacing 0 3 6 inches 15 cm 3 10 12 inches 30 cm 10 20 24 inches 60 cm 20 50 36 inches 90 cm 50 100 48 inch...

Page 15: ...d wire to the ground rod or plate s wire If the ground rod or plate is not pre wired use a 10 AWG bare copper wire 5 Drive a 5 8 by 8 17mm x 2 5m copper clad steel rod into well moistened soil not les...

Page 16: ...Max B C 500 150m Max D 1000 300m Max Figure 10 For upgrades of existing systems we recommend adding one ground point Detail A at the end of each main communication line valve box black white DEC SG LI...

Page 17: ...to the controller 2 Connect the cable wires to the Pressure Sensor Terminals labeled C in Figure 11 Red wire to the terminal black wire to the terminal 3 Place the controller s switch to ON Master Val...

Page 18: ...of splicing device Using an appropriate splicing kit such as Scotchcast 82 A1 or equivalent is recommended Placing the cable splice in a small valve box for protection and accessibility is a good inst...

Page 19: ...nd cabinet Smart Hubs are interchangeable with each other Layout 1 Local The SmartHub is attached to the Field Interface Unit by a Wireline The SmartHub typically resides in the office with the Lynx c...

Page 20: ...1 2 3 4 MENU POWER AUTO LYNX SmartHub 1 SmartHub 2 Wired Lynx 1 2 3 The Wireline connection is limited to about 9 miles Layout 3 Wireless The Lynx SmartHub DEC RS 1000 DR digital radio and modem comm...

Page 21: ...ton Figure 15 C 5 Click Start Operations button Figure 15 D Certain SmartHub information should be displayed on the screen Figure 16 If communication fails the software will display a fail message Fig...

Page 22: ...eboot computer 3 Plug USB cable into a USB port and Serial port on radio Figure 18 4 Connect Phoenix power cable into 12V power supply Plug other end into DC IN port on radio Figure 19 5 Plug in 12V p...

Page 23: ...nation selection is handled through the Personal Communications Industry Association PCIA 800 759 0300 and an application must be submitted to the FCC There is a PCIA fee and FCC license fee that must...

Page 24: ...rams or other settings that impact watering Off Mode When placed in Off mode the SmartHub will not execute any watering operation whether it is program or manually initiated Any watering operation wil...

Page 25: ...diagnostic information See page 33 10 Station Settings button allows you to modify station parameters Within this setting you can disable the station from any activity hold station watering for a spec...

Page 26: ...will save any setting modifications and return the user to the Home display Home display examples The GW line displays the address of the controller In the example above the address of the SmartHub is...

Page 27: ...ion page 31 Press the Stop button to cancel Pause Button The Pause button can be used to pause any running irrigation program or all irrigation activity Stop Button Use the Stop function to cancel all...

Page 28: ...s This command resets all station settings by selecting Yes After selecting Yes press the Up or Down Arrows to activate There is a short countdown before the command executes during which the command...

Page 29: ...nds Sta Delay This setting sets the station delay in seconds before any individual station activates This feature helps avoid water hammer Max Sim Sta This setting sets the maximum number of simultane...

Page 30: ...he station to edit in this field Choose from Station 01 through the SmartHub maximum station count of 500 LSM or 250 GAC Allows the operator to set the percent adjust for the selected station if desir...

Page 31: ...ne when plants trees or lawn need extra water A new sod lawn for example would benefit from a grow in program for a couple of weeks or month 5 For interval schedules it is necessary to define today s...

Page 32: ...ub to implement changes SBF Lists are disabled when the controller is in Local Mode Manual Watering The Manual Watering functions are used for additional watering if the irrigation program is not suff...

Page 33: ...rst value For our example select station 12 5 Press the Right Arrow to advance the cursor to the next entry field This entry field will indicate the runtime in hours and minutes HH MM Use the Input Di...

Page 34: ...display the date and time of the last power down PD and last power up PU Press the Down arrow to scroll down the informations Menu PowerUp Detect DC 2 500 DB 1 1 0 0 PD 01 11 19 14 22 20 PU 01 12 19 0...

Page 35: ...command allows the user to run diagnostic tests that send messages to decoders and modules The faceplate will show the last test performed at the TM The tests include communication pictured solenoid...

Page 36: ...ot RSSI is Received Signal Strength Indication Menu Radio Settings Radio Power 040 Radio Addr 1181 RSSI Enable No Set Radio Dflts No Menu Radio Frequencies Displays the radio s send and receive freque...

Page 37: ...they are on D1L1 0 24A D1L2 0 24A D2L1 0 24A D2L2 0 24A The display will also show the load currents by individual wires of a two wire communication line 1 open 0 2 open 0 The display will show the Ra...

Page 38: ...ffected daughterboard s alarm LED blinks on and off Phase Current Imbalance Alarm D1L1 High Amp D2 A 0 500 D1L1 A 0 750 D2 A 0 500 Triggered when load current of one wire is 2x higher than the opposit...

Page 39: ...butor or outside the United States call 951 688 9221 Neither Toro nor Toro Warranty Company is liable for indirect incidental or consequential damages in connection with the use of equipment including...

Page 40: ...ion www toro com 1 877 345 8676 Form Number 373 0965 Rev C WARNING Cancer and Reproductive harm www P65Warnings ca gov For more information please visit www toro com CAProp65 Patent www ttcopats com 4...