30310468 Issue 1.05
Features
Cable checking for inputs and outputs.
Normally-open (NO) or normally-close (NC) output
automatically follows Input port to change state.
Electronically addressing. Addresses can be
modified in field.
DIN-Rail mounted or Wall mounted.
Standard: EN 54-18:2005
Description
DI-9319E Digital Zone Monitor Unit (the Unit) is
designed to connect with conventional detectors,
occupying one address. When any device in the loop
reports alarm signal, the Unit will transmit the signal to
the FACP which generates fire alarm and displays the
address of the Unit.
Connection and Cabling
Fig. 1 shows terminals of the Unit.
Fig. 1
(Z1, Z2) IN & OUT: Connect with the loop of FACP,
polarity-insensitive.
(V, G) IN & OUT: Connect with 24VDC power, V
connects with a positive terminal and G with a negative
terminal.
I, G: Connect with conventional detectors.
E: Ground cable. This terminal shall not be connected
when the 24V power circuit provides cable checking.
Otherwise, it shall be connected to ground.
COM, NO, NC: Dry Output terminals. COM and NO are
normally open contacts, COM and NC are normally
closed contacts ( note: there is 20kΩ between COM
and NO)
.
CODE: Connect with the programmer.
Recommended Wiring:
1.0mm
2
or above fire cable for
all terminals. Subject to local codes.
Installation
Warning: Before installing the Unit,
disconnect power from the loop and verify
that the guide rail is securely installed.
1)
Before installation, make sure the enclosure is in
good condition and markings are complete.
2)
The module can be mounted on a 35mm DIN-Rail
as shown on Fig. 2.
3)
The module can also be wall mounted by 4
mounting screws as shown in Fig. 3.Mouting
space is 67×40.5mm.
Fig. 2
Fig. 3
Application
The output loop can connect up to 30 conventional
devices. Smoke, heat and combination detectors, such
as DC-9101E Detector, DC-9102E Detector, DC-9103E
DI-9319E
Digital Zone Monitor Unit
Monitor Unit
2831-CPR-F2023
GST-0018-01