GST DI-9319E Quick Start Quide Download Page 2

 

30310468                                                                                                                                                                        Issue 1.05

 

Detector,  C-9101  Detector,  C-9102  Detector,  C-9103 
Detector and

 

  C-9104 Detector can be used together. 

The parameters of the Unit can be programmable by a 

programmer in field.   

Programming Parameters

 

In  standby  state  of  the  programmer,  pressing 

Fn

  and 

then number 3, “—“ (data waiting for programming) will 

be popped up on the screen. Writing a parameter and 

then pressing “Program”, a “P” will show on the screen 

meaning the parameter is programmed.   
Press Fn and then number 3, output checking methods 

can be set.   

No checking 

others(Default) 

Checking 

The relationship between the input port resistance and 
the product state is shown in the following table: 

I/G port 

Resistance 

Input state

 

0 - 

100Ω 

Short fault 

110 - 

1.4kΩ 

Alarm 

1.5 - 

10kΩ 

Normal 

11 kΩ 

Open fault 

The  relationship  between  the  output  port  voltage  and 
the product state is shown in the following table: 

Output port voltage 

Output state 

< 8 V 

Fault 

> 9 V 

Normal 

If the output end connects with end-of-line resistor, the 
system connection is shown in Fig. 4. 

NO

COM

NC

Controlled Devices

I+

G

DI

-9319E 

D

igi

tal 

Z

one M

oni

tor 

U

ni

t

Conventional Detectors

Conventional Detectors

4.7k

Ω 

End-

of-l

ine 

Re

si

st

or

Fig. 4 

If  the  NO  and  COM  terminals  do  not  connect  the 
controlled  device,  the  DC24V  power  supply  on  the 
controller is needed, the system connection is shown in 
Fig. 5. 

NO

COM

NC

DC24V Power Supply

I+

G

DI

-9319E

 D

igi

ta

l Z

o

n

e

 M

o

n

ito

U

n

it

Conventional Detectors

Conventional Detectors

4.7k

Ω 

E

nd-of

-lin

e Re

si

sto

r

V1

V2

 

Accessories and Tools

 

Model 

Name 

Remark 

P-9910B 

Hand 

Held 

Programmer 

Order 
separately 

RT-0.25W-4.7k
Ω±5%-25mm 

Resistor 

Provided 

 

Specification 

Operating Voltage 

Loop: 24VDC (16VDC-28VDC) 
Power: 24VDC(20VDC-28VDC) 

Standby Current 

Loop≤ 0.38mA   
mA    Power≤ 10mA 

Action Current 

Loop ≤ 0.39mA 
Power≤ 60mA 

Output Capacity 

2A@30VDC   

Relay Output 

NO or NC 

Input Capacity 

Up to 30 conventional detectors 

Programming 
Method 

Electronically  addressed.  Code 
range is within 1 - 242. 

Indicators 

Alarm  LED:  Red, illuminates in 
fire  condition,  quiet  when  24V 
power is off and flashes in other 
states. 
Fault LED: Yellow, it turns  0.5s 
on,  0.5s  off  when  input  fault 
occur,  0.2s  on  and  0.2s  off 
when  output  faults  occur,  0.1s 
on  and  0.9s  off  when  ground 
fault  occurs.  It  lights  steadily 
when  loop  faults  occur  and  it 
turns off in other states.   

Ingress  Protection 
Rating 

IP30 

Operating 
Temperature 

-

10°C - +55°C 

Relative Humidity 

≤ 95%, non-condensing 

Compatible 
DIN-Rail 

35mm DIN-Rails 

Material  and  Color 
of Enclosure 

ABS, white (RAL9016) 

Dimension 
(L×W×H) 

85.3mm×78mm×33mm 

Weight 

About 74.1g   

Limited Warranty 

GST

 warrants that the product will be free of charge for 

repairing or replacing from defects in design, materials 
and  workmanship  during  the  warranty  period.  This 
warranty shall not apply to  any product that is found to 
have been improperly installed or used in any way not in 
accordance  with  the  instructions  supplied  with  the 
product.  Anybody,  including  the  agents,  distributors  or 
employees, is not in the position to amend the contents 
of this warranty. Please contact your local distributor for 
products not covered by this warranty.

 

 