30310468 Issue 1.05
Detector, C-9101 Detector, C-9102 Detector, C-9103
Detector and
C-9104 Detector can be used together.
The parameters of the Unit can be programmable by a
programmer in field.
Programming Parameters
:
In standby state of the programmer, pressing
Fn
and
then number 3, “—“ (data waiting for programming) will
be popped up on the screen. Writing a parameter and
then pressing “Program”, a “P” will show on the screen
meaning the parameter is programmed.
Press Fn and then number 3, output checking methods
can be set.
1
No checking
others(Default)
Checking
The relationship between the input port resistance and
the product state is shown in the following table:
I/G port
Resistance
Input state
0 -
100Ω
Short fault
110 -
1.4kΩ
Alarm
1.5 -
10kΩ
Normal
>
11 kΩ
Open fault
The relationship between the output port voltage and
the product state is shown in the following table:
Output port voltage
Output state
< 8 V
Fault
> 9 V
Normal
If the output end connects with end-of-line resistor, the
system connection is shown in Fig. 4.
NO
COM
NC
Controlled Devices
I+
G
DI
-9319E
D
igi
tal
Z
one M
oni
tor
U
ni
t
Conventional Detectors
Conventional Detectors
4.7k
Ω
End-
of-l
ine
Re
si
st
or
Fig. 4
If the NO and COM terminals do not connect the
controlled device, the DC24V power supply on the
controller is needed, the system connection is shown in
Fig. 5.
NO
COM
NC
DC24V Power Supply
I+
G
DI
-9319E
D
igi
ta
l Z
o
n
e
M
o
n
ito
r
U
n
it
Conventional Detectors
Conventional Detectors
4.7k
Ω
E
nd-of
-lin
e Re
si
sto
r
V1
V2
Accessories and Tools
Model
Name
Remark
P-9910B
Hand
Held
Programmer
Order
separately
RT-0.25W-4.7k
Ω±5%-25mm
Resistor
Provided
Specification
Operating Voltage
Loop: 24VDC (16VDC-28VDC)
Power: 24VDC(20VDC-28VDC)
Standby Current
Loop≤ 0.38mA
mA Power≤ 10mA
Action Current
Loop ≤ 0.39mA
Power≤ 60mA
Output Capacity
2A@30VDC
Relay Output
NO or NC
Input Capacity
Up to 30 conventional detectors
Programming
Method
Electronically addressed. Code
range is within 1 - 242.
Indicators
Alarm LED: Red, illuminates in
fire condition, quiet when 24V
power is off and flashes in other
states.
Fault LED: Yellow, it turns 0.5s
on, 0.5s off when input fault
occur, 0.2s on and 0.2s off
when output faults occur, 0.1s
on and 0.9s off when ground
fault occurs. It lights steadily
when loop faults occur and it
turns off in other states.
Ingress Protection
Rating
IP30
Operating
Temperature
-
10°C - +55°C
Relative Humidity
≤ 95%, non-condensing
Compatible
DIN-Rail
35mm DIN-Rails
Material and Color
of Enclosure
ABS, white (RAL9016)
Dimension
(L×W×H)
85.3mm×78mm×33mm
Weight
About 74.1g
Limited Warranty
GST
warrants that the product will be free of charge for
repairing or replacing from defects in design, materials
and workmanship during the warranty period. This
warranty shall not apply to any product that is found to
have been improperly installed or used in any way not in
accordance with the instructions supplied with the
product. Anybody, including the agents, distributors or
employees, is not in the position to amend the contents
of this warranty. Please contact your local distributor for
products not covered by this warranty.