English
1. Is the pipe diameter suitable?
2. Has the trap been installed within the allowable inclination and with the arrow on the body
pointing in the direction of flow?
3. Has sufficient space been secured for maintenance?
4. Have maintenance valves been installed at the inlet and outlet? If the outlet is subject to
back pressure, has a check valve been installed?
5. Is the inlet pipe as short as possible, with as few bends as possible, and installed so that the
condensate will flow naturally down into the trap?
6. Has the piping work been done with the proper methods, as shown in the table on page 8?
Check to make sure that the pipes connected to the trap have been installed properly.
Operational inspections should be performed at least twice per year, or as called for by trap
operating conditions. Steam trap failure may result in temperature drop in the equipment, poor
product quality or losses due to steam leakage.
6. Inspection and Maintenance
WARNING
NEVER apply direct heat to the float. The float may explode due to
increased internal pressure, causing accidents leading to serious injury or
property and equipment damage.
• Installation, inspection, maintenance, repairs, disassembly, adjustment
and valve opening/closing should be carried out only by trained
maintenance personnel.
• Before attempting to open the trap, close the inlet and outlet isolation
valves and wait until the trap has cooled completely. Failure to do so
may result in burns.
• Be sure to use the proper components and NEVER attempt to modify
the product.
CAUTION
Body, Cover
Gaskets
X-element
Screen
Float
Air Vent Valve Seat, Orifice
Model
Cover Bolt 9
Orifice 4
Screen
Holder 7
Drain Plug 10
X-element Cover 19
Air Vent Valve Seat 16
Orifice Plug 20
Check inside for damage, dirt, grease, oil film, rust or scale
Check for warping or damage
Check for damage
Check for clogging, corrosion or damage
Check for deformation, damage, oil film or water inside
Check for rust, scale, oil film, wear or damage
Parts Inspection Procedure
Tightening Torques and Distance Across Flats
SJ_FNX
SJ_FVX, SJ3V-X
SJ5FNX
SJ5FVX
SJ6FNX
SJ6FVX
SJ7FNX
SJ7FVX
SJ3FNX
SJ3FVX, SJ3V-X
N
•
m
40
40
140
140
30*
140
35
140
N
•
m
60
50
140
140
30*
140
35
140
N
•
m
90
120
400
30*
140
35
400
N
•
m
100
120
400
30*
140
35
400
mm
22
30
50
12
32
19
50
mm
24
30
50
12
32
19
50
mm
13
17
24
38
12
32
19
38
mm
17
19
24
38
12
32
19
38
1 N m
5
10 kg cm
* Indicates torque values with a sealing tape wrapped 3 – 3.5 times around the threads of the
plug or drain plug
If drawings or other special documentation were supplied for the product, any torque given there
takes precedence over values shown here.