Descriptions of functions: Pulse/frequency/switch output
Assign frequency
output
NOTE: This function is available when the operating mode is
set to “frequency output”.
Select process variable for frequency output
• Off
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality (Steam dryness)
• Total mass flow
• Energy flow
• Heat flow difference
Select units for
assigned process
variable
Select units for the process variable assigned to frequency
output.
NOTE: See 8.2.11 for details.
Minimum frequency
value
NOTE: This function is available when the operating mode is
set to “frequency output”.
Enter the minimum frequency value.
Setting range: 0.0 to 1000.0 Hz
Factory setting: 0.0 Hz
Maximum
frequency value
NOTE: This function is available when the operating mode is
set to “frequency output”.
Enter the maximum frequency value.
Setting range: 0.0 to 1000.0 Hz
Factory setting: 1000.0 Hz
Measuring value at
minimum frequency
NOTE: This function is available when the operating mode is
set to “frequency output”.
Enter measured value for minimum frequency. (Signed
floating-point number)
Factory setting: 0
Measuring value at
maximum frequency
NOTE: This function is available when the operating mode is
set to “frequency output”.
Enter measured value for maximum frequency. (Signed
floating-point number)
Factory setting: 0
Failure mode
NOTE: This function is available when the operating mode is
set to “frequency output”.
Define output behavior in alarm condition.
• Actual value
• Defined value
• 0 Hz
Factory setting: 0 Hz
Failure frequency
NOTE: This function is available when the operating mode is
set to “frequency output”.
Enter frequency output value in alarm condition.
Setting range: 0.0 to 1250.0 Hz
Factory setting: 0.0 Hz
Invert output signal
NOTE: This function is available when the operating mode is
set to “frequency output”.
Invert the output signal.
• No
• Yes
Factory setting: No