172-65639M-01 (EF200) 13 Apr 2018
72
Operating conditions for displaying the following diagnostics information:
•
Diagnostics information 871: The process temperature is less than 2K from
the saturated steam line.
•
Diagnostics information 872: The measured steam quality (steam dryness)
has dropped below the configured limit value for the steam quality (steam
dryness) (limit value: "Expert" menu
→
System
→
Diagnostic handling
→
Diagnostic limits
→
Steam quality limit).
•
Diagnostics information 873: The process temperature is ≤ 0 °C.
•
Diagnostics information 874: Steam dryness fraction calculation is outside
the specified limits for the following process parameters: pressure,
temperature, velocity.
•
Diagnostics information 972: The degree of superheat has exceeded the
configured limit value (limit value: "Expert" menu
→
System
→
Diagnostic
handling
→
Diagnostic limits
→
Degrees of superheat limit).
10.4 Overview of information events
Unlike a diagnostic event, an information event is displayed in the event
logbook only and not in the diagnostic list.
Info number
Info name
I1000
-------- (Device ok)
I1079
Sensor changed
I1089
Power on
I1090
Configuration reset
I1091
Configuration changed
I1092
Trend data deleted
I1110
Write protection switch changed
I1137
Electronic changed
I1151
History reset
I1154
Reset terminal voltage min/max
I1155
Reset electronic temperature
I1156
Memory error trend
I1157
Memory error event list
I1185
Display backup done
I1186
Restore via display done
I1187
Settings downloaded with display
I1188
Display data cleared
I1189
Backup compared
I1227
Sensor emergency mode activated
I1228
Sensor emergency mode failed
I1256
Display: access status changed
I1264
Safety sequence aborted
I1335
Firmware changed
I1397
Fieldbus: access status changed
I1398
CDI: access status changed
I1444
Device verification passed
I1445
Device verification failed
I1459
Failed: I/O module verification
I1461
Failed: Sensor verification
I1512
Download started
I1513
Download finished
I1514
Upload started
I1515
Upload finished
I1552
Failed: Main electronic verification
I1553
Failed: Pre-amplifier verification