Back-to-back mounting
In a back-to-back arrangement it is recommended to mount the CEDD
®
HPS Basestations on an H-profile
structure. This allows cool air to flow into the base of the equipment, and warm air to flow out of the top of
the equipment; the middle horizontal bar (6 in the drawing below) blocks the return of warm air from the back
of the equipment. There should be no horizontal bars blocking air flow to the top or bottom of the equipment.
Wall mounting
When mounted on a wall, minimum clearances are required (see table below). Clearance from the wall must
be created by mounting on vertical constructive profiles, leaving the space (minimum 80 mm) between the
cabinet and the wall at the top and bottom open for airflow. The cabinet should not be mounted on horizontal
profiles, which would reduce airflow around the intake and outlet.
Clearances for adequate airflow
Pos. Description
Values
1
Top and bottom clearance
Min. 250 mm
2
Left and right clearance
Min. 100 mm
3
Distance from the wall
Min. 80 mm
4
Hot air exhaust
50 mm
5
Cool air intake
90 mm
6
Airflow block
Needed to prevent recirculation of warm air from
outlet to inlet
•
The CEDD
®
HPS Basestation's cooling air intake and outlet areas must be kept free
from obstruction.
Installation and Maintenance Manual - CEDD
®
HPS Basestation
©
TKH Airport Solutions 2022. All rights reserved. All specifications subject to change without notice.
19