background image

8  

PRE-INSTALLATION 

Inspect the equipment making sure that all parts and accessories are accounted for.  Check 

equipment against order and packing list. 

  If the equipment has been sitting in storage for some time, inspect for moisture and/or dust 

accumulation.  Both can cause damage to electrical components as well as bearings and insulation. 

 

Verify that electric service matches equipment ratings.  Verify that heating or cooling 

medium capacities match associated equipment (boiler, chiller, condensing unit, ...)  

INSTALLATION CODES 

Care  taken  during  the  installation  and  start-up  is  vital  to  the  longevity  and  reliability  of  the 

equipment.  Confirm that gas and electric utilities match the rating on the equipment name plate. 

 

This heater shall be installed in accordance with local codes or, in the absence of 
local code, according to National Fuel Gas Code, ANSI Z223.1/ NFPA 54, or the 
CAN/ CSA B149.1 Natural Gas and Propane Installation Code. 

 

If the heater is to be installed in an aircraft hangar, refer to ANSI/NFPA 409. 

 

If the heater is to be installed in a parking structure, refer to ANSI/NFPA 88A. 

 

If the heater is to be installed in a service garage, refer to ANSI/NFPA 88B. 

 

For installations in Canada, refer to CAN/CSA B149.1 National Gas and Propane 
Installation Codes. 

 

Gas  piping  and  exhaust  venting  must  be  sized  and  installed  to  comply  with 
applicable codes and standards.

 

 

 

If in doubt regarding the application of the heater, contact a sales representative 
or the factory. 

GAS PIPING 

 Supply gas pressure must be 7” – 14” w.c. 

HEAT EXCHANGER VENTING 

 

 

The National Fuel Gas Code ANSI Z223.1/NFPA 54 specifies a 4 foot horizontal vent terminal 

clearance from gas and electrical meters, regulators and relief openings. 

Exhaust  vent  within  air 

handler  vestibule  needs  to  be  insulated  to  avoid  excessive  temperatures  within the  control 
cabinet  that  can  cause  component  failure

.  Refer  to  Heatco’s  installation  manual  for  more 

information.

 

 

POSITIONING THE HEATER 

Locate  the  heater  exactly  level,  making  certain  minimum  clearance  required  by  local  codes  is 

maintained between the heater and any combustible materials.  See name plate on equipment for 
minimum recommended clearances. 

NOTE:  If  the  heater  is  installed  in  a  garage,  it  shall  be  installed  with  a  clearance 
above the floor of 18 inches. 

When the air handler equipment is located on a roof or at ground level on a concrete pad, the 

equipment intake needs to be a minimum of 24” above the roof and/ or ground to prevent the intake 
of  snow  or  splashed  rain.  The  equipment  should  be  located  in  such  a  way  to  prevent  prevailing 
winds from blowing directly into the equipment intake. If the application is critical, provisions must be 
made to protect the equipment inlet from the driving winds.  

Summary of Contents for TA-109

Page 1: ......

Page 2: ......

Page 3: ...void in event the product is improperly installed and or operated under conditions other than normal published ratings improperly maintained misused or not in compliance with applicable codes or not...

Page 4: ...rvation and are not intended to supplant requirements of federal state or local codes having jurisdiction These codes should be reviewed before installation of equipment All equipment must be installe...

Page 5: ...8 BLOWER WHEEL 28 PLATE FINNED COIL CLEANING 29 CONDENSATE TRAP 29 GENERAL START UP INFORMATION 30 SPECIFIC EQUIPMENT DETAILS pages not numbered EQUIPMENT SPECIFICATION EQUIPMENT DRAWING SEQUENCE OF O...

Page 6: ...ondensation Also check for damage caused by rodents and be sure to eliminate any dust that may have built up on the components while the equipment was in storage LONG TERM STORAGE Please observe the f...

Page 7: ...otor sheave However some equipment may still utilize a variable pitch motor sheave on motors up to 30 Hp INDIRECT FIRED HEATING BURNER INFORMATION Titan Air Handlers can be equipped with inshot style...

Page 8: ...es Gas piping and exhaust venting must be sized and installed to comply with applicable codes and standards If in doubt regarding the application of the heater contact a sales representative or the fa...

Page 9: ...side of the equipment Review the equipment submittal drawing for the correct direction of the coil pull CURBING OUTDOOR MOUNTING The use of a full perimeter curb or mounting rails under the heater is...

Page 10: ...of the blower A properly designed duct transition from the blower outlet to a larger duct is recommended for long ducts or ducts with numerous elbows The equipment was designed for a specific CFM and...

Page 11: ...r coil piping is typically arranged to provide counterflow operation supply piping on lower air leaving side of coil and return on upper air entering side See Diagram on the right Verify that equipmen...

Page 12: ...itional sensor wiring may be required Carefully review the schematic and associated schematic symbol legend Note that legend may be on the parts legend sheet rather than on the schematic If an intake...

Page 13: ...g Options Recommended option for supporting accessories on a flat roof Other method of installation using sheet metal support legs IMPORTANT Not recommended for any unit larger than 125 model Typical...

Page 14: ...be found packaged in either a clear plastic bag or corrugated box NOTICE There may be more than one package of assembly materials provided 1 Apply provided caulk tape to the face of the joint to be bo...

Page 15: ...ed together caulk the external section seam s to provide a water tight seal IMPORTANT Check all external sheet metal seams for caulk shrinkage and re caulk if necessary Titan Air Inc does not warranty...

Page 16: ...washers Check all sections of the unit thoroughly for assembly hardware The assembly hardware will be found packaged in either a clear plastic bag or corrugated box NOTICE There may be more than one p...

Page 17: ...ction letter on the service side of the unit with the corresponding letter on the other section In addition also refer to the unit submittal drawing for proper assembly order 4 Lift blower section and...

Page 18: ...TANT Re caulk unit lifting lugs after assembly Check all external sheet metal seams for caulk shrinkage and re caulk if necessary Titan Air Inc does not warranty water damage equipment Unit seam seali...

Page 19: ...entry of snow rain and include an intake screen to meet ANSI standards Accessories on large equipment may be shipped in two pieces for field assembly As a result two damper actuators may need to be f...

Page 20: ...h the hood to the filter section except in step five substitute inch bolts in for self taping screws to attach the hood to the filter section 7 After all of the accessories are installed caulk each se...

Page 21: ...Titan Air highly recommends the discharge damper be mounted so the blades are orientated vertically If possible IMPORTANT Titan Air also highly recommends the discharge damper be mounted at the wall o...

Page 22: ...d diffuser is supplied by others Support diffuser at two points using field supplied materials See example below Square Tubing DISCHARGE DAMPER Secure turning vanes once adjusted in the field by other...

Page 23: ...t determine whether the drain pan is under negative or positive pressure DESIGN CONSIDERATION Calculate static pressure at the drain pan for worst case scenario Refer to the diagrams on the next page...

Page 24: ...1 inch wg B A 5 C A B Pipe Diameter inches Insulation if applicable POSITIVE PRESSURE P TRAP CALCULATIONS D Minimum 1 2 inch E 1 2 inch Maximum Total Static Pressure F D E Pipe Diameter inches Insulat...

Page 25: ...rocedure once per year FILTERS Dirty or clogged filters will restrict air flow which in turn affects the equipment performance Therefore it is necessary to check filters on a regular basis Several sta...

Page 26: ...alignment and belt tension are critical to belt and bearing service life Incorrect belt tension or misalignment of sheaves can cause any of the following Premature failure of bearings Premature failur...

Page 27: ...aves and then re tighten If a face width variation exists measure the difference between each side of the narrowest sheave and adjust until both sides are an equal distance from the straight edge BELT...

Page 28: ...ns of dirt or moisture lubrication may be required every 6 months to 1 year Refer to website for specific manufacturer cut sheets pertaining to motor bearing maintenance Typical motor bearing lubricat...

Page 29: ...ll also provide an initial check for pinholes or cracks that may not be visible Refrigerant leak detectors should be utilized for DX coils NOTICE Corrosion or deposits on copper or brazed joints may i...

Page 30: ...eration per the sequence of operation must be verified Apparent malfunction of a component may be caused by improper supply conditions field wiring errors or other problems unrelated to the component...

Reviews: