background image

10  

 

Exercise care when moving the equipment.   

 

Rig the equipment using 

ALL

 the lifting points, in a fashion that holds it level and 

prevents it from tipping, falling and/ or twisting.  

 

Spreader bars of sufficient width 

MUST

 be used across the top of the equipment, 

to ensure that the lifting cables clear equipment cabinetry.  

 

Utilize the same rigging and lifting methods as the ones applied to the equipment, 
for lifting the accessories.  

 

Remove  all  wooden  shipping  blocks  before  setting  equipment  onto  curb  (If 
applicable). 

 

After  sections  are  set  in  place,  assemble  according  to  Equipment  Section 
Assembly. (If applicable) 

 

NOTICE:  Warranty  does  not  cover  damage  from  the  equipment  being 
severely twisted or dropped during handling. 

DUCTWORK 

Ductwork must be sized and installed in accordance with applicable codes and standards.  As a 

recommendation follow  SMACNA  guides  for  proper  ductwork  design,  size and installation.    A  size 
variation  may  exist  from  recommended  duct  size  to  equipment  or  accessory  flange  size.  
Accessories  on  the  equipment  intake  or  discharge  may  be  larger  than  the  openings  on  the 
equipment. Be sure to check the equipment submittal drawing for the correct equipment connection 
size.  Recommended duct size applies to the size of the duct at the connection to the equipment. 
Factory  also  recommends  2  1/2  times  the  equivalent

 

duct  diameters  of  straight  ductwork  off  the 

discharge outlet of the blower. A properly designed duct transition from the blower outlet to a larger 
duct is recommended for long ducts or ducts with numerous elbows. The equipment was designed 
for  a  specific  CFM  and  ESP  (External  Static  Pressure)  stated  on  equipment  rating  plate.  The 
ductwork attached to the equipment will significantly affect its performance. 

On  heaters  mounted  outdoors,  discharge  ductwork  should  be  insulated  to  minimize 

condensation  during  the  “off”  cycle  in  cold  weather.    A  fresh  air  intake  hood  with  bird  screen  is 
required.  Discharge ductwork on a twin blower equipment must be common to both blowers. 

On  a  heater  mounted  indoors  with  through  the  roof  intake,  a  “mushroom”  type  intake  hood  is 

recommended  to  prevent  moisture  entrainment.    When  using  “through  the  wall”  intake  duct,  the 
intake louver should have adequate moisture baffling characteristics.  All intake ductwork exposed to 
the  heated  space  should  be  insulated.  Also  any  ductwork  passing  through  unconditioned  spaces 
must be insulated and covered with a vapor barrier. 

SOUND AND VIBRATION CONTROL 

Use  of  flex  coupler  between  building  ductwork  and  air  makeup  equipment  is  highly 

recommended.    Vibration  isolators  that  mount  between  the  equipment  and  support  structure  are 
optional and can be supplied with the equipment for installation by others.  Another option is internal 
isolation of the blower/motor assembly with internal flexible connections between the blower housing 
and the equipment structure. 

Appropriate insulation on the interior of ductwork significantly reduces sound levels. Blower 

selection also plays a major role. 

Summary of Contents for TA-109

Page 1: ......

Page 2: ......

Page 3: ...void in event the product is improperly installed and or operated under conditions other than normal published ratings improperly maintained misused or not in compliance with applicable codes or not...

Page 4: ...rvation and are not intended to supplant requirements of federal state or local codes having jurisdiction These codes should be reviewed before installation of equipment All equipment must be installe...

Page 5: ...8 BLOWER WHEEL 28 PLATE FINNED COIL CLEANING 29 CONDENSATE TRAP 29 GENERAL START UP INFORMATION 30 SPECIFIC EQUIPMENT DETAILS pages not numbered EQUIPMENT SPECIFICATION EQUIPMENT DRAWING SEQUENCE OF O...

Page 6: ...ondensation Also check for damage caused by rodents and be sure to eliminate any dust that may have built up on the components while the equipment was in storage LONG TERM STORAGE Please observe the f...

Page 7: ...otor sheave However some equipment may still utilize a variable pitch motor sheave on motors up to 30 Hp INDIRECT FIRED HEATING BURNER INFORMATION Titan Air Handlers can be equipped with inshot style...

Page 8: ...es Gas piping and exhaust venting must be sized and installed to comply with applicable codes and standards If in doubt regarding the application of the heater contact a sales representative or the fa...

Page 9: ...side of the equipment Review the equipment submittal drawing for the correct direction of the coil pull CURBING OUTDOOR MOUNTING The use of a full perimeter curb or mounting rails under the heater is...

Page 10: ...of the blower A properly designed duct transition from the blower outlet to a larger duct is recommended for long ducts or ducts with numerous elbows The equipment was designed for a specific CFM and...

Page 11: ...r coil piping is typically arranged to provide counterflow operation supply piping on lower air leaving side of coil and return on upper air entering side See Diagram on the right Verify that equipmen...

Page 12: ...itional sensor wiring may be required Carefully review the schematic and associated schematic symbol legend Note that legend may be on the parts legend sheet rather than on the schematic If an intake...

Page 13: ...g Options Recommended option for supporting accessories on a flat roof Other method of installation using sheet metal support legs IMPORTANT Not recommended for any unit larger than 125 model Typical...

Page 14: ...be found packaged in either a clear plastic bag or corrugated box NOTICE There may be more than one package of assembly materials provided 1 Apply provided caulk tape to the face of the joint to be bo...

Page 15: ...ed together caulk the external section seam s to provide a water tight seal IMPORTANT Check all external sheet metal seams for caulk shrinkage and re caulk if necessary Titan Air Inc does not warranty...

Page 16: ...washers Check all sections of the unit thoroughly for assembly hardware The assembly hardware will be found packaged in either a clear plastic bag or corrugated box NOTICE There may be more than one p...

Page 17: ...ction letter on the service side of the unit with the corresponding letter on the other section In addition also refer to the unit submittal drawing for proper assembly order 4 Lift blower section and...

Page 18: ...TANT Re caulk unit lifting lugs after assembly Check all external sheet metal seams for caulk shrinkage and re caulk if necessary Titan Air Inc does not warranty water damage equipment Unit seam seali...

Page 19: ...entry of snow rain and include an intake screen to meet ANSI standards Accessories on large equipment may be shipped in two pieces for field assembly As a result two damper actuators may need to be f...

Page 20: ...h the hood to the filter section except in step five substitute inch bolts in for self taping screws to attach the hood to the filter section 7 After all of the accessories are installed caulk each se...

Page 21: ...Titan Air highly recommends the discharge damper be mounted so the blades are orientated vertically If possible IMPORTANT Titan Air also highly recommends the discharge damper be mounted at the wall o...

Page 22: ...d diffuser is supplied by others Support diffuser at two points using field supplied materials See example below Square Tubing DISCHARGE DAMPER Secure turning vanes once adjusted in the field by other...

Page 23: ...t determine whether the drain pan is under negative or positive pressure DESIGN CONSIDERATION Calculate static pressure at the drain pan for worst case scenario Refer to the diagrams on the next page...

Page 24: ...1 inch wg B A 5 C A B Pipe Diameter inches Insulation if applicable POSITIVE PRESSURE P TRAP CALCULATIONS D Minimum 1 2 inch E 1 2 inch Maximum Total Static Pressure F D E Pipe Diameter inches Insulat...

Page 25: ...rocedure once per year FILTERS Dirty or clogged filters will restrict air flow which in turn affects the equipment performance Therefore it is necessary to check filters on a regular basis Several sta...

Page 26: ...alignment and belt tension are critical to belt and bearing service life Incorrect belt tension or misalignment of sheaves can cause any of the following Premature failure of bearings Premature failur...

Page 27: ...aves and then re tighten If a face width variation exists measure the difference between each side of the narrowest sheave and adjust until both sides are an equal distance from the straight edge BELT...

Page 28: ...ns of dirt or moisture lubrication may be required every 6 months to 1 year Refer to website for specific manufacturer cut sheets pertaining to motor bearing maintenance Typical motor bearing lubricat...

Page 29: ...ll also provide an initial check for pinholes or cracks that may not be visible Refrigerant leak detectors should be utilized for DX coils NOTICE Corrosion or deposits on copper or brazed joints may i...

Page 30: ...eration per the sequence of operation must be verified Apparent malfunction of a component may be caused by improper supply conditions field wiring errors or other problems unrelated to the component...

Reviews: