93
93
SIF5600 - Manual - 03 - 2008
Framing:
ENUM[ 1] Pulse Blout
0 Off
1 30 s
2 10 s
3 1 s
4 100 ms
5 50 ms
default: 0
Dimension : 1 register
Synopsis : class WREG -> ADR=44 (NUM=45), DIM=1
WREG NUM=46 Description : 52 local
Framing:
ENUM[ 1] 52 local
0 Off
1 On
default: 1
Dimension : 1 register
Synopsis : class WREG -> ADR=45 (NUM=46), DIM=1
WREG NUM=47 Description : 52 remote
Framing:
ENUM[ 1] 52 remote
0 Off
1 On
default: 0
Dimension : 1 register
Synopsis : class WREG -> ADR=46 (NUM=47), DIM=1
WREG NUM=48 Description : 52 check
Framing:
ENUM[ 1] 52 check
0 Off
1 On
default: 1
Dimension : 1 register
Synopsis : class WREG -> ADR=47 (NUM=48), DIM=1
SECTION 8 COMMAND MESSAGES INDEX
Following WREG accomplish COMMANDS.
WREG NUM=5 Command codes:
1 Clear
2 Store
3 PAR default
WREG NUM=6 Command codes:
3 REE default
WREG NUM=7 Codici di comando:
0 Test off
1 Test I> no-trip
2 Test I>> no-trip
3 Test IE> no-trip
4 Test IE>> no-trip
4097 Test I> trip
4098 Test I>> trip
4099 Test IE> trip
4100 Test IE>> trip
WREG NUM=8 Command codes:
1 Reset counters
2 Reset events
4 Reset led-relay
WREG NUM=10 Command codes:
1 Open 52
2 Close 52
Section 9 DEFAULTS
This section collects factory default data.
WREG NUM=1 Address 1 (1)