88
88
SIF5600 - Manual - 03 - 2008
WREG NUM=13 Description : Measures reading
Framing:
ENUM[ 1] Reading
0 Relative
1 Direct
default: 1
Dimension : 1 register
Synopsis : class WREG -> ADR=12 (NUM=13), DIM=1
WREG NUM=14 Description : K1 configuration
Framing:
B32 [ 1] K1
bit 0 Self test
bit 1 PW break Blin1
bit 2 CB fail
bit 3 PW shorted
bit 4 Start I>
bit 5 Start I>>
bit 6 Start IE>
bit 7 Start IE>>
bit 8 Trip I>
bit 9 Trip I>>
bit 10 Trip IE>
bit 11 Trip IE>>
bit 12 Open 52
bit 13 Close 52
bit 14 Self test 52
default: 0x00000000
ENUM[ 3] K1 mode
0 DeEn-NoLatch
1 DeEn-Latch
2 En-NoLatch
3 En-Latch
default: 0
Dimension : 3 registers
Synopsis : class WREG -> ADR=13 (NUM=14), DIM=3
WREG NUM=15 Description : K1 timer
Framing:
INT [ 1] tTR1 (1=10 ms)
1,99 step 1
100
default: 20
Dimension : 1 register
Synopsis : class WREG -> ADR=14 (NUM=15), DIM=1
WREG NUM=16 Description : K2 configuration
Framing:
B32 [ 1] K2
bit 0 Self test
bit 1 PW break Blin1
bit 2 CB fail
bit 3 PW shorted
bit 4 Start I>
bit 5 Start I>>
bit 6 Start IE>
bit 7 Start IE>>
bit 8 Trip I>
bit 9 Trip I>>
bit 10 Trip IE>
bit 11 Trip IE>>
bit 12 Open 52
bit 13 Close 52
bit 14 Self test 52
default: 0x00000000
ENUM[ 3] K2 mode
0 DeEn-NoLatch
1 DeEn-Latch
2 En-NoLatch
3 En-Latch
default: 0
Dimension : 3 registers
Synopsis : class WREG -> ADR=15 (NUM=16), DIM=3
WREG NUM=17 Description : K2 timer