Following parameters are user-programmable:
Pre-trigger and post-trigger time
Selected sampled quantities.
Analog channels (1...12) allocation.
Digital channels (1...12) allocation (output relay and/or binary inputs).
Trigger setup; the information storage starts when a state transition on the selected signal occurs.
(protective element start and/or trip, output relay and/or binary input switching).
Alarm: when the 80% of the buffer space is reached an alarm may be issued. The system being
of linear type, the records are back-to-back recorded to the end of available memory; the alarm
output is a warning in order that the user may download the data RAM
[1]
to clear memory for new
records
COMTRADE
Records are recorded in COMTRADE format; (Common Format for Transient Data); This is a standard
for the data exchange for various types of tests or simulation datas, etc, for power system applica-
tions.
The measurements are recorded in ASCII or BINARY format. COMTRADE fi les always come by
pairs:
The “.CFG”-fi le describing the confi guration: number of analog and digital channels, sampling rate,
scale factors, etc.
The “.DAT”-fi le containing the data
The COMTRADE is part of IEC 60255-24 standard.
The recording can be analyzed by mean of ThySetter sw or any other standard compliant viewer.
The record quantity is depending on settings of following parameters:
Pre-trigger and post-trigger times
Number of allocated channels.
By means of the following formula the record quantity may be evaluated:
where:
N
: record quantity
v
i
: sampled measures
v
RMS
: analog measures (RMS)
n
B
: logic variables
t
pre
: pre-trigger time interval
t
post
: post-trigger time interval
f
: frequency
Example 1
With the following setting:
Pre-trigger:
0.2
s
Post-trigger:
0.1 s
Sampled measures:
i
L1
,
i
L2
,
i
L3
,
i
E
Analog measures:
I
L1
,
I
L2
,
I
L3
,
I
E
Logic variables:
K1, K2, K3, K4, K5, K6, IN1, IN2
819 record can be stored if f = 50 Hz, since:
Example 2
With following setting:
Pre-trigger:
0.5
s
Post-trigger:
0.5 s
Sampled data:
i
L1
,
i
L2
,
i
L3
,
i
E
Analog channels:
I
L1
,
I
L2
,
I
L3
,
I
E
Digital channels:
K1, K2, K3, K4, K5, K6, IN1, IN2
up to 204 records can be stored if f = 60 Hz, since:
Note 1 Data are stored into volatile memory RAM, they are lost when power goes down
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
trigger.ai
Trigger oscillografia
Trigger
Time
pre-trigger
post-trigger
trigger.ai
Trigger oscillografia
Trigger
Time
pre-trigger
post-trigger
N
= int
·
24 + 24
v
i
+ 4
v
RMS
+
n
B
600
(
t
pre
+
t
post
)(s)
59 s
·
f
(Hz)
50 (Hz)
N
= int
·
24 + 24
v
i
+ 4
v
RMS
+
n
B
600
(
t
pre
+
t
post
)(s)
59 s
·
f
(Hz)
50 (Hz)
N
= int
= 819
·
24 + 24 · 4 + 4 · 4 + 8
600
(0.1 + 0.2 )(s)
59 s
·
50 (Hz)
50 (Hz)
N
= int
= 819
·
24 + 24 · 4 + 4 · 4 + 8
600
(0.1 + 0.2 )(s)
59 s
·
50 (Hz)
50 (Hz)