18
18
NA11 - Manual - 02 - 2009
TECHNICAL DATA
10.0...100.0 s (step 0.1 s)
I
> Reset time delay (
t
>
RES
)
0.00...100.0
s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Defi nite time
50/51 First threshold defi nite time (
I
>
def
) 0.100...35.0
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...9.99
I
n
(step 0.01
I
n
)
10.0...35.0
I
n
(step 0.1
I
n
)
I
>
def
within CLP (
I
CLP>def
)
0.100...35.0
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...9.99
I
n
(step 0.01
I
n
)
10.0...35.0
I
n
(step 0.1
I
n
)
I
>
def
Operating time (
t
>
def
)
0.04...200.00
s
0.04...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...200 s (step 1 s)
Inverse time
[1]
50/51 First threshold inverse time (
I
>
inv
)
0.100...20.00
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...20.00
I
n
(step 0.01
I
n
)
I
>
inv
within CLP (
I
CLP>inv
) 0.100...20.00
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...20.00
I
n
(step 0.01
I
n
)
I
>
inv
Operating time (
t
>
inv
)
0.02...60.0
s
0.02...9.99 s (step 0.01 s)
10.0...60.0 s (step 0.1 s)
I>> Element
I
>> Curve type (
I>>
Curve
) DEFINITE
or
I
2
t
I
CLP
>> Activation time (
t
CLP>>
)
0.00...100.0
s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
I
>> Reset time delay (
t
>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Defi nite time
50/51 Second threshold defi nite time (
I
>>
def
)
0.100...35.0
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...9.99
I
n
(step 0.01
I
n
)
10.0...35.0
I
n
(step 0.1
I
n
)
I
>>
def
within CLP (
I
CLP>>def
)
0.100...35.0
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...9.99
I
n
(step 0.01
I
n
)
10.0...35.0
I
n
(step 0.1
I
n
)
I
>>
def
Operating time (
t
>>
def
)
0.03...10.00 s (step 0.01 s)
Inverse time
50/51 Second threshold inverse time (
I
>>
inv
)
0.100...20.00
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...20.00
I
n
(step 0.01
I
n
)
I
>>
inv
within CLP (
I
CLP>>inv
)
0.100...20.00
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...20.00
I
n
(step 0.01
I
n
)
I
>>
inv
Operating time (
t
>>
inv
)
0.02...10.00 s (step 0.01 s)
Note 1
Standard Inverse Time (IEC 255-3/BS142 type A or SIT):
t = 0.14 · t>
inv
/ [(I/I>
inv
)
0.02
- 1]
Very Inverse Time (IEC 255-3/BS142 type B or VIT):
t = 13.5 · t>
inv
/ [(I/I>
inv
) - 1]
Extremely Inverse Time (IEC 255-3/BS142 type C or EIT):
t = 80 · t>
inv
/ [(I/I>
inv
)
2
- 1]
Moderately Inverse (ANSI/IEEE type MI):
t = t>
inv
· {0.01 / [(I/I>
inv
)
0.02
- 1] + 0.023}
Very Inverse (ANSI/IEEE type VI):
t = t>
inv
· {3.922 / [(I/I>
inv
)
2
- 1] + 0.098}
Extremely Inverse (ANSI/IEEE type EI):
t = t>
inv
· {5.64 / [(I/I>
inv
)
2
- 1] + 0.024}
I-squared-t
(I
2
t = K):
t = 16 · t>
inv
/ (I/I>
inv
)
2
Electromechanical (EM):
t = 0.28 · t>
inv
/ [-0.236 · (I/I>
inv
)
-1
+ 0.339]
RECTIFIER (RI):
t = 2351 · t>
inv
/ [(I/I>
inv
)
5.6
- 1]
t
:
operate time
I>
inv
:
pickup
value
t>
inv
:
operate time setting
Asymptotic reference value:
1.1
I
>
inv
Minimum operate time:
0.1
s
Equation is valid for 1.1 ≤ I/I>
inv
≤ 20
With
I>
inv
pickup ≥
2.5
I
n
, the upper limit is
35
I
n
Summary of Contents for NA11
Page 189: ...189 NA11 Manual 02 2009 APPENDIX...