FUNCTION CHARACTERISTICS
The trip of
I
E
> element may be inhibited by the start of the second and/or third el-
ement (
I
E
>>,
I
E
>>>) by setting
ON
the Disable IE> by start IE>>, Disable IE> by
start IE>>> (
IE>disbyIE>>, IE>disbyIE>>>
) parameters available inside the
Set \ Profi le A(or B)\ Residual overcurrent-50N/51N \ IE>> Element
(
IE>>> Element) \ Setpoints
menus.
Similarly the trip of the
I
E
>> element may be inhibited by start of the third element (
I
E
>>>) by setting
ON
the Disable IE>> by start IE>>> (
IE>>disbyIE>>>
) parameter available inside the
Set \ Profi le
A(or B) \ Residual overcurrent-50N/51N \ IE>>> Element \Setpoints
menu.
All the named parameters can be set separately for
Profi le A
and
Profi le B
(
Set \ Profi le A(or B)\
Residual overcurrent-50N/51N \
IE> Element
(
IE>> Element
,
IE>>> Element) \ Setpoints
menus).
An adjustable reset time delay is provided for every threshold
t
E>RES
,
t
E>>RES
,
t
E>>>RES
).
Each residual overcurrent element can produce the Breaker Failure output if the
IE> BF
,
IE>> BF
and/or
IE>>> BF
parameters are set to
ON.
The parameters are available inside the
Set\Pro-
fi le A(or B)\ Residual overcurrent-50N/51N \
IE> Element
(
IE>> Element
,
IE>>> Element) \Setpoints
menus.
[1]
For all overcurrent elements, a block from the second harmonic restraint may be set by setting
ON
the
IE>2ndh-REST, IE>>2ndh-REST, IE>>>2ndh-REST
parameters inside the
Set\Pro-
fi le A(or B)\ Residual overcurrent-50N/51N \
IE> Element
(
IE>> Element
,
IE>>> Element) \Setpoints
menus.
If the CLP function (Cold Load Pick-up) is enabled for element blocking, the selected threshold may
be blocked for an adjustable time interval, starting from the circuit breaker closure.
This operating mode may be select by setting
ON-Element blocking
the
IECLP> Mode, IECLP>>
Mode, IECLP>>> Mode
parameters.
If the CLP function (Cold Load Pick-up) is enabled for threshold change, the selected threshold may
be changed for an adjustable time interval, starting from the circuit breaker closure.
This operating mode (
ON-Change setting =
IECLP> Mode, IECLP>> Mode, IECLP>>>
Mode
) and the concerning operating time within the CLP (
tECLP>, tECLP>>, tECLP>>>
) may
be adjusted inside the
Set\Profi le A(or B)\ Residual overcurrent-50N/51N \
IE> Element
(
IE>> Element
,
IE>>> Element) \ Setpoints menus
, whereas the operating thresholds within the CLP (
IECLP>def,
IECLP>inv,....
) may be adjusted inside the
Set\Profi le A(or B)\ Residual overcurrent-50N/51N \
IE> Element
(
IE>> Element
,
IE>>> Element) \ Defi nite time (Inverse time)
menus.
For every of the four thresholds the following block criteria are available:
Logical block (Block1)
If the
IE>BLK1, IE>>BLK1
and/or
IE>>>BLK1
enabling parameters are set to
ON
and a bi-
nary input is designed for logical block (Block1), the concerning element is blocked off whenever
the given input is active.
[2]
The enabling parameters are available inside the
Set\Profi le A(or B)\
Residual overcurrent-50N/51N \
IE> Element
(
IE>> Element
,
IE>>> Element) \Setpoints
menus, while
the
Block1
function must be assigned to the selected binary input inside the
Set\Inputs\Binary input
IN1(2)
menus.
Selective block (Block2)
All along the protective elements the selective block may be set.
The logic selectivity function may be performed by means any combination of the following I/O:
One committed pilot wire input (BLIN1).
One or more binary inputs designed for input selective block.
One committed pilot wire output (BLOUT1).
One or more output relays designed for output selective block.
Note 1 The common settings concerning the Breaker failure protection are adjustable inside the
Breaker Failure - BF
menu.
Note 2 The exhaustive treatment of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside
CONTROL AND MONITOR-
ING
section
•
•
•
•
Timers-F50N-51N.ai
IE> element residual overcurrent (50N/51N) - Timers
IE> Start
IE> Trip
t
E>
t
E>
RESET
INPUT
t
E>RES
t
E>RES
t
E>RES
t
Timers-F50N-51N.ai
IE> element residual overcurrent (50N/51N) - Timers
IE> Start
IE> Trip
t
E>
t
E>
RESET
INPUT
t
E>RES
t
E>RES
t
E>RES
t