173
NA11 - Manual - 02 - 2009
APPENDIX
Description
Parameter
Unit
Setting range
Pickup value
In
0.05 ... 1.00 step = 0.01
BF Residual current threshold
State
OFF | ON
Pickup value
IEn
0.01 ... 2.00 step = 0.01
BF Time delay
Value
s
0.06 ... 10.00 step = 0.01
BF Logical block
BF-BLK1
OFF | ON
BF Start from circuit breaker
CB Input
OFF | ON
BF Start relays
BF-ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
BF Trip relays
BF-TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
BF Start LEDs
BF-ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 | L9
| L10
BF Trip LEDs
BF-TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 | L9
| L10
Profi le B
Thermal protection with RTD thermometric probes - 26
PT1 Probe
ThAL1 Alarm
ThAL1 Enable
ThAL1 Enable
OFF | ON
26 PT1 Alarm threshold
ThAL1
^C
0 ... 200 step = 1
ThAL1 Operating time
Value
s
0 ... 100 step = 1
ThAL1 Alarm relays
ThAL1-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
ThAL1 Alarm LEDs
ThAL1-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 | L9
| L10
Th>1 Trip
Th>1 Enable
Th>1 Enable
OFF | ON
26 PT1 Trip threshold
Th>1
^C
0 ... 200 step = 1
Th>1 Operating time
Value
s
0 ... 100 step = 1
Th>1 Breaker failure
Th>1BF
OFF | ON
Th>1 Trip relays
Th>1-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Th>1 Trip LEDs
Th>1-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 | L9
| L10
PT2 Probe
ThAL2 Alarm
ThAL2 Enable
ThAL2 Enable
OFF | ON
26 PT2 Alarm threshold
ThAL2
^C
0 ... 200 step = 1
ThAL2 Operating time
Value
s
0 ... 100 step = 1
ThAL2 Alarm relays
ThAL2-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
ThAL2 Alarm LEDs
ThAL2-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 | L9
| L10
Th>2 Trip
Th>2 Enable
Th>2 Enable
OFF | ON
26 PT2 Trip threshold
Th>2
^C
0 ... 200 step = 1
Th>2 Operating time
Value
s
0 ... 100 step = 1
Th>2 Breaker failure
Th>2BF
OFF | ON
Th>2 Trip relays
Th>2-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Th>2 Trip LEDs
Th>2-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 | L9
| L10
PT3 Probe
ThAL3 Alarm
ThAL3 Enable
ThAL3 Enable
OFF | ON
26 PT3 Alarm threshold
ThAL3
^C
0 ... 200 step = 1