MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 89 Thomson Technology
6180 Start attempts
No.
Setting
Min. setting
Max. setting Factory
setting
6181 Start attempts
Attempts
1
10
3
6182 Start attempts
Relay output A
R0 (none)
R0 (none)
6183 Start attempts
Relay output B
R0 (none)
Option
dependent
R0 (none)
6184 Start attempts
Fire start attempt
1
10
7
6185 Start attempts
FP cool down
0.0 s
990.0 s
30.0 s
6190 f/U OK
No.
Setting
Min. setting
Max. setting Factory
setting
6191 f/U OK
Timer
1.0 s
99.0 s
5.0 s
6200 f/U failure
No.
Setting
Min. setting
Max. setting Factory
setting
6201 f/U failure
Timer
1.0 s
99.0 s
30.0 s
6202 f/U failure
Relay output A
R0 (none)
R0 (none)
6203 f/U failure
Relay output B
R0 (none)
Option
dependent
R0 (none)
6210 Stop
No.
Setting
Min. setting
Max. setting Factory
setting
6211 Stop
Cool down time
0.0 s
990.0 s
240.0 s
6212 Stop
Extended STOP
1.0 s
99.0 s
5.0 s
6213 Stop
Coil type
STOP
RUN
RUN
6220 Stop failure
No.
Setting
Min. setting
Max. setting Factory
setting
6221 Stop failure
Timer
10.0 s
120.0 s
30.0 s
6222 Stop failure
Relay output A
R0 (none)
R0 (none)
6223 Stop failure
Relay output B
R0 (none)
Option
dependent
R0 (none)
6250 GB control
No.
Setting
Min. setting
Max. setting Factory
setting
6251 GB control
Timer t
GBC
0.0 s
30.0 s
2.0 s
6260 P
nom
derate
No.
Setting
Min. setting
Max. setting Factory
setting
6261 P
nom
derate
Input
4…20mA
VDO/PT100 4…20mA
6262 P
nom
derate
Start derate
0
20000
16 units
6263 P
nom
derate
Derate slope
0.1%/U
100.0%/U
5.0%/U
6264 P
nom
derate
Proportional
OFF
ON
OFF
6265 P
nom
derate
Enable
OFF
ON
OFF
6266 P
nom
derate
Derate limit
0.0%
100.0%
80.0%
The number of start attempts adjusted in menu 6184 Fire start attempt, is used
when the digital input ‘fire pump’ is used instead of the setting 6181.