![THOMSON MEC 320 Operating Manual Download Page 90](http://html1.mh-extra.com/html/thomson/mec-320/mec-320_operating-manual_1108996090.webp)
MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 90 Thomson Technology
6310 Idle running
No.
Setting
Min. setting
Max. setting Factory
setting
6311 Idle running
Start timer
0.0 min
999.9 min
300.0 min
6312 Idle running
Enable start timer
OFF
ON
OFF
6313 Idle running
Stop timer
0.0 min
999.9 min
300.0 min
6314 Idle running
Enable stop timer
OFF
ON
OFF
6315 Idle running
Idle relay
Option dependent
R0 (none)
6316 Idle running
Enable
OFF
ON
OFF
6400 Master clock
No.
Setting
Min. setting
Max. setting Factory
setting
6401 Master clock
Start hour
0
23
8
6402 Master clock
Stop hour
0
23
8
6403 Master clock
Difference
0.1Hz
1.0Hz
0.1Hz
6404 Master clock
Set point
1 s
999 s
20 s
6405 Master clock
Enable
OFF
ON
OFF
6410 Battery test
No.
Setting
Min. setting
Max. setting Factory
setting
6411 Battery test
Set point
8.0V DC
32.0V DC
18.0V DC
6412 Battery test
Delay
1 s
300 s
20 s
6413 Battery test
Output A
R0 (none)
6414 Battery test
Output B
Option dependent
R0 (none)
6415 Battery test
Enable
OFF
ON
OFF
6420 Voltage trip
No.
Setting
Min. setting Max. setting Factory
setting
6421 Voltage trip
Type
Phase-phase Phase-neutral Phase-phase
Summary of Contents for MEC 320