MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 81 Thomson Technology
4130 Fuel level 1 (4…20mA input 102.1)
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
4131 4…20mA input 102.1 Set point
0%
120%
-
10%
4132 4…20mA input 102.1 Timer
0.0 s
600.0 s
-
120.0 s
4133 4…20mA input 102.1 Relay output A R0 (none)
-
R0 (none)
4134 4…20mA input 102.1 Relay output B R0 (none)
Option
dependent -
R0 (none)
4135 4…20mA input 102.1 Enable
OFF
ON
RUN
OFF
4136 4…20mA input 102.1 Fail class
Alarm (1) Trip MB (6) -
Warning (2)
4140 Fuel level 2 (4…20mA input 102.2)
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
4141 4…20mA input 102.2 Set point
0%
120%
-
10%
4142 4…20mA input 102.2 Timer
0.0 s
600.0 s
-
120.0 s
4143 4…20mA input 102.2 Relay output A R0 (none)
-
R0 (none)
4144 4…20mA input 102.2 Relay output B R0 (none)
Option
dependent -
R0 (none)
4145 4…20mA input 102.2 Enable
OFF
ON
RUN
OFF
4146 4…20mA input 102.2 Fail class
Alarm (1) Trip MB (6) -
Warning (2)
4170 VDO 104.1
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
4171 VDO 104.1
Set point
0.0 bar
10.0 bar
-
4.0 bar
4172 VDO 104.1
Timer
0.0 s
100.0 s
-
5.0 s
4173 VDO 104.1
Relay output A R0 (none)
-
R0 (none)
4174 VDO 104.1
Relay output B R0 (none)
Option
dependent -
R0 (none)
4175 VDO 104.1
Enable
OFF
ON
RUN
OFF
4176 VDO 104.1
Fail class
Alarm (1) Trip MB (6) -
Warning (2)
4180 VDO 104.2
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
4181 VDO 104.2
Set point
0.0 bar
10.0 bar
-
5.0 bar
4182 VDO 104.2
Timer
0.0 s
100.0 s
-
5.0 s
4183 VDO 104.2
Relay output A R0 (none)
-
R0 (none)
4184 VDO 104.2
Relay output B R0 (none)
Option
dependent -
R0 (none)
4185 VDO 104.2
Enable
OFF
ON
RUN
OFF
4186 VDO 104.2
Fail class
Alarm (1) Trip MB (6) -
Trip/stop (4)
4190 VDO 105.1
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
4191 VDO 105.1
Set point
40 deg.
150 deg.
-
100 deg.
4192 VDO 105.1
Timer
0.0 s
100.0 s
-
5.0 s
4193 VDO 105.1
Relay output A R0 (none)
-
R0 (none)
4194 VDO 105.1
Relay output B R0 (none)
Option
dependent -
R0 (none)
4195 VDO 105.1
Enable
OFF
ON
RUN
OFF
4196 VDO 105.1
Fail class
Alarm (1) Trip MB (6) -
Warning (2)
Summary of Contents for MEC 320
Page 2: ......