MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 87 Thomson Technology
6060 Gen-set modes
No.
Setting
Setting
Factory
setting
6061 Gen-set mode
Island operation
Island operation
-
Gen-set mode
AMF
AMF
AMF
Gen-set mode
Peak shaving
Peak shaving
-
Gen-set mode
Fixed power
Fixed power
-
Gen-set mode
Mains power export
Mains power export -
Gen-set mode
Load take over
Load take over
-
6070 Date and time (internal clock) setting
No.
Setting
Min. setting Max. setting Factory
setting
6071 Date and time
Year
2001
2100
6072 Date and time
Month
1
12
6073 Date and time
Day
1
31
6074 Date and time
Weekday
1
7
6075 Date and time
Hour
0
23
6076 Date and time
Minute
0
59
Depending on
the software
version
6080 Counters
The settings below (except kWh) are offset values that need to be adjusted at the
commissioning if the display is used for reading the values. A breaker operation is counted each
time the breaker closes.
The setting ‘reset kWh counter’ resets the value of the produced kWh.
No.
Setting
Min. setting Max. setting Factory
setting
6081 Counters
Running time
0
20000
0
6082 Counters
GB operations
0
20000
0
6083 Counters
MB operations
0
20000
0
6084 Counters
kWh
OFF
ON
OFF
6085 Counters
Start attempts
0
20000
0
6090 Service timer
The function of the service timer enables the user to get an alarm when service of the gen-set is
needed. The timer is reset when the alarm is acknowledged or when the timer is disabled and
enabled again.
No.
Setting
Min. setting Max. setting Factory
setting
6091 Service timer
Set point
0 h
9000 h
500 h
6092 Service timer
Relay output A
R0 (none)
R0 (none)
6093 Service timer
Relay output B
R0 (none)
Option
dependent
R0 (none)
6094 Service timer
Enable
OFF
ON
ON
6095 Service timer
Fail class
Alarm (1)
Trip MB (6)
Warning (2)
The date and time can easily be synchronized with the present time and date
from the utility software.