MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 46 Thomson Technology
G 439 440 440V
1010 Reverse Power
Setpoint -5.0 %
LIM DEL OA OB ENA FC
first entry
G 439 440 440V
1020 Over current 1
Setpoint 115.0 %
LIM DEL OA OB ENA FC
G 439 440 440V
Enter passw. 1999
ENTER
G 439 440 440V
1011 Reverse power
-50.0 -5.0 0.0%
RESET SAVE
Yes
No
BACK
SEL
INCREASE NO
DECREASE NO
Increase setting
Decrease setting
moves the cursor
G 439 440 440V
PROTECTION SETUP
SET POINT 1 SETUP
PROT1 PROT2
SEL
BACK
Mode overview
The unit has four different running modes and one block mode. For detailed information see
page 9.
Auto
In auto mode the unit will operate automatically, and the operator cannot initiate any sequences
manually.
Semi-auto
In semi-auto mode the operator has to initiate all sequences. This can be done via the push-
button functions, modbus commands or digital inputs. When started in semi-automatic mode,
the gen-set will run at nominal values.
Test
The test sequence will start when the test mode is selected.
Manual
When manual mode is selected, the binary increase/decrease inputs can be used (if they have
been configured) as well as the start and stop push-buttons. When starting in manual mode, the
gen-set will start without any subsequent regulation.