MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 57 Thomson Technology
VDO input 105
This VDO input is used for measuring the cooling water temperature.
VDO sensor
type
Temperature
Type 1
Type 2
Type 3
Type 4
°C
40
291.5
480.7
69.3
Point 1
50
197.3
323.6
Point 2
60
134.0
222.5
36.0
Point 3
70
97.1
157.1
Point 4
80
70.1
113.2
19.8
Point 5
90
51.2
83.2
Point 6
100
38.5
62.4
11.7
Point 7
110
29.1
47.6
Point 8
120
22.4
36.8
7.4
130
28.9
140
22.8
150
18.2
Level switch type
VDO sensor type
Type 3
Resistance
Function
<1.7k
Normal situation, no alarm
>1.7k
Alarm situation
VDO input 106
This VDO input is used for the fuel level sensor.
VDO sensor type
Type 1
Value
Resistance
0%
78.8
100%
1.6
VDO sensor type
Type 2
Value
Resistance
0%
3
100%
180
The configurable type is configurable with 8 points.
If the VDO input is used as a level switch, then be aware that no voltage must be
connected to the input. If any voltage is applied to the VDO inputs, then it will be
damaged. Refer to the Application Notes for further wiring information.
If the VDO input is used as a level switch, then be aware that no voltage must be
connected to the input. If any voltage is applied to the VDO inputs, then it will be
damaged. Refer to the Application Notes for further wiring information.