FLAME DETECTION TRESHOLD
In this parameter the manufacturer sets the flame's detection threshold. Beneath the pre-set
threshold's value, the burner detects the vanishing of the flame. The parameter is set in the
bracket of 5 to 90%.
Manufacturer Advice:
10%
FURNACE PROTECTION (OVERHEAT)
In this parameter, the user sets the furnace's temperature which protects from the overheating.
The protection is activated when a higher temperature than the one that was previously set is
reached and when the CH pump is turned off. The driver starts the CH pump automatically and
switches off the burner. The protection of the furnace from the overheating is set in the bracket
of 60 to 90 ºC. The furnace's protection can be activated when:
working of room thermostat and simultaneously surpassing the protection temperature
of the furnace,
setting
”Summer”
function and simultaneously surpassing the protection temperature
of the furnace,
setting the
”STOP”
mode and simultaneously surpassing the protection temperature of
the furnace,
surpassing the temperature of the heating water over 90ºC.
Manufacturer Advice:
80-90ºC
STB TEMPERATURE
It is the temperature where the Overheating Alarm is activated. At the same time the controller
activates the CH pump and the WUW pump. For water boiler the default value is 90
o
C.
If sensor type PT is chosen then, the value of this parameter can change depending the
application.
IGNITION STABILIZATION
When ignition has occurred, the air-fan works for the time, which has been set by this parameter.
This operation drives the ignition gases out of the boiler faster.
Manufacturer Advice:
60-120sec
MAXIMUM BURNER POWER
In this parameter the installer can set the maximum burner power, where the user can set by
visiting the burner's menu. This prevents the user to set the burner at a maximum power, than
the one it is required by the system.
Manufacturer Advice:
50kW for MPB 50 and 80kW for MPB 80