background image

2

Item Quantity

Description

1

1

RTV Tube

2

1

Power Connection Boot

3

2

Conductor Wire Pins

4

1

Braid Wire Pin

5

1

Ground Sleeve

6

1

End Cap

7

1

Tape Strip (PETK-3-ECM only)

8

1

Grommet (PETK-3-ECM only)

9

1

End Termination Caution Label

Tools Required . . .

Certifi cations/Approvals . . . 

Kit Contents . . .

1

2

6

4

3

8

5

7

9

1

2

6

4

3

8

5

7

9

Item Quantity

Description

1

1

Expediter Assembly
    Support Cap with O-Ring
    Threaded Grommet Compressor
    Grommet
    Support Base with O-Ring

2

1

Junction Box Lid

3

1

Junction Box Base with O-Ring

4

1

Nut

5

1

Banding

6

1

Banding Guide

7

1

Electronic Control Module w/ Terminal Blocks

(Refer to terminal speci

fi

 cations for maximum allowable wire size)

ECM Type*
C - Controler
L - Limiter
CL - Controller/Limiter

* The maximum pipe exposure temperature is limited to 232°C

8

1

Junction Box Lid Cord

9

3

Blind Plug

Terminator-LN-Tool
(order separately)

3 mm
8 mm

28 mm

Warnings . . .

• Due to the risk of electrical shock, arcing and 

fi

 re 

caused by product damage or improper usage, 

installation or maintenance, a ground-fault protection 

device is required. 

• Installation must comply with Thermon requirements 

(including form PN 50207U for Ex systems) and be 

installed in accordance with the regulations as per the 

norm EN IEC 60079-14 for hazardous areas (where 

applicable), or any other applicable national and local 

codes. 

• Component approvals and performance ratings are 

based on the use of Thermon speci

fi

 ed parts only.

• De-energize all power sources before opening 

enclosure.

• Avoid electrostatic charge. Clean only with a damp 

cloth.

• Keep ends of heating cable and kit components dry 

before and during installation.

• Minimum bending radius of heating cable is 32 mm 

(except HPT is 57 mm and FP is 19 mm). 

• Individuals installing these products are responsible 

for complying with all applicable safety and health 

guidelines. Proper Personal Protective Equipment 

(PPE) should be utilized during installation. Contact 

Thermon if you have any additional questions.

Order Separately . . .
PETK Power and End Termination Kits (per cable)

PETK-1

for RSX, VSX, BSX

PETK-2

for KSX, HTSX

PETK-3-ECM

for HPT, FP

The following installation procedures are suggested 
guidelines for the installation of the Terminator ECM-P-XP Kit.

Receiving, Storing and Handling . . .

1.  Inspect materials for damage incurred during shipping.
2.  Report damages to the carrier for settlement.
3.  Identify parts against the packing list to ensure the 

proper type and quantity has been received.

4.  Store in a dry location.

Dimensions . . .

205mm

II 2 (2) G Ex eb mb [ib] IIC T4, Ex tb IIIC T135°C SIRA 12ATEX5239X
II 2 (2) D Ex tb IIIC T135°C IP66 Db

International Electrotechnical Commission

IEC Certifi cation Scheme for Explosive Atmospheres
SIR 12.0103X 

Terminator

TM

 ECM-P-XP

 

INSTALLATION PROCEDURES

1725        

II 2 GD  Ex eb mb [ib]ib I

IC T4, Ex tb I

IIC T135°C

               S

IRA 12A

TEX5239X

IP66

-60

°

C  

  Ta 

  + 55

°

C

IECEx S

IR 12.0103X Ex eb mb [ib]ib I

IC T4, Ex tb 

IIIC T135°C

PN 27673

Do

 no

t ope

n while energized. See in

sta

llat

ion

 in

st

ru

ct

io

ns

Te

r

mi

nator E

CM

 

Fo

us

as

 an

 ad

just

able 

electronic contro

l m

od

ule

Crimp Tool 2,5mm

2

Summary of Contents for Terminator ECM-P-XP

Page 1: ...ib IIC T4 Ex tb IIIC T135 C PN 27673 D o not open while energized See installation instructio n s T e rminator EC M F o r u s e as an adjustable electronic control m o d u l e TheHeatTracingSpecialists TerminatorTM ECM P XP Electronic Control Module INSTALLATION PROCEDURES For Connection 1 2 Heating Cables Applications ...

Page 2: ...e energize all power sources before opening enclosure Avoid electrostatic charge Clean only with a damp cloth Keep ends of heating cable and kit components dry before and during installation Minimum bending radius of heating cable is 32 mm except HPT is 57 mm and FP is 19 mm Individuals installing these products are responsible for complying with all applicable safety and health guidelines Proper ...

Page 3: ...with grommet provided in PETK 3 ECM 4 Slide expediter toward pipe and route cable through support base entry 8 Terminate cable with appropriate PETK termination kit Refer to PETK installation instructions 9 Push excess cable back through expediter Tighten cap securely Tape cable expansion loop to pipe 6 Mount expediter to pipe using pipe band Do not band over cable 7 Cut off end of cable Terminato...

Page 4: ...nstall junction box lid and twist hand tight Insert screwdriver into ratchet slots located on side of junction box base 17 Lid latch mechanism fully engaged To remove lid repeat step 16 but in the opposite direction The Heat Tracing Specialists 15 Use the rotary switches for settling Control and Limit Temperature Celsius or Fahrenheit and Auto or Manual reset Control switches on Type C Limiter swi...

Page 5: ...ble Layout Tips Insert two cables into expediter Note For HPT and FP cable exchange grommet in Terminator with grommet provided in PETK 3 ECM Wiring Details Connection 1 or 2 Heating Cables L L N N C NO NC Comm Port Alarm Relay Main supply Heater output B B A A B B RTD Limiter Sensor RTD Controller Sensor GND 1 2 TerminatorTM ECM P XP INSTALLATIONPROCEDURES ...

Page 6: ...on jusqu au point de blocage 17 La sécurité de blocage est complètement engagée Pour ouvrir le boîtier répéter l étape 16 mais dans l autre sens de rotation Deutsch Terminator ECM P XP Elektronisches Regelmodul INSTALLATIONSANWEISUNG Für Temperatursteuerung anschluss 1 bis 2 Heizkabel Warnhinweise Wegen der Risiken eines Stromschlags eines Funkendurchschlags oder eines Feuers die durch Produktbesc...

Page 7: ...s calefactores Advertencias Debido al riesgo de descargas eléctricas arcos eléctricos y fuego causados por daños en el producto o incuorrecta manipulación instalación o mantenimiento se requiere proteger el circuito mediante un diferencial La instalación debe cumplir con los requisitos de Thermon incluyendo el estándar PN 50207U para sistemas Ex y debe instalarse acorde a las regulaciones según la...

Page 8: ...erdere kabels 2 Voer de RTD voeler s in het doorvoerrubber Trek niet aan het uiteinde van de RTD voeler als deze door het doorvoerrubber in de opvoersok doorgevoerd wordt Trek aan het draadgedeelte de voeler door 3 Steek de kabel door het rubber en de opvoersok heen Zorg ervoor dat de knooppunt in de verwarmingskabel betreffende HPT and FP zich buiten de voet bevinden Let op Voor HPT en FP dient h...

Reviews: