TC 816 Operation Manual
THERMON…The Heat Tracing Specialists
®
Operation Manual 0503 E TC 816
Page 35 of 42
4.3
Zone Parameters configured by heat tracing supplier
4.3.1
Parameter P16:
LIM ADDR
This Parameter is:
•
Valid for Temperature Controller Zones
- Zones 1 through 16
- unit in: TC 816 communication address
•
Not
valid for
Limiter Zones
•
Not
valid for
Current Zones
To each temperature controller Zone a heat tracing cable temperature limiter Zone can be assigned. Accord-
ing to the EN 50 014 standard for electrical equipment in hazardous area the limiter Zone needs to be utilised
by a separate electronic controller. Within the TC 816 multi circuit temperature controller concept that can be
any other TC 816 controller set up as a heat tracing cable temperature limiter (see chapter 1.1.3).
With parameter P16 the communication address (
LIM ADDR
) of the heat tracing cable temperature lim-
iter is set. In case no limiter Zone is assigned to the controller Zone the
LIM ADDR
is set to “0”.
Adjustment thresholds: 0...30
Default value:
0 (no limiter Zone assigned)
4.3.2
Parameter P17:
LIM ZONE
This Parameter is:
•
Valid for Temperature Controller Zones
- Zones 1 through 16
- unit in: heat tracing cable temperature limiter Zone number
•
Not
valid for
Limiter Zones
•
Not
valid for
Current Zones
With parameter P17 the Limiter Zone (
LIM ZONE
) number of the heat tracing cable temperature limiter
(see chapter 4.3.1) is assigned to the controller Zone.
Adjustment thresholds: 1...16
Default value:
same number as temperature controller Zone number