IM 05P01F31-11EN  page 1/10

Contents

1.  Safety Precautions

2.  Model and Suffix Codes

3.  How to Install

4.  Hardware Specifications

5.  How to Connect Wires

6.  Terminal Wiring Diagrams

Introduction

Thank you for purchasing the UT32A Digital Indicating Controller (Entry model).

This operation guide describes the basic operations of the UT32A. The guide should 

be provided to the end user of this product.

Be sure to read this operation guide before using the product in order to ensure 

correct operation.

For details of each function, refer to the electronic manual. Before using the product, 

refer to the table of Model and Suffix Codes to make sure that the delivered product 

is consistent with the model and suffix codes you ordered. Also make sure that the 

following items are included in the package.

• Digital Indicating Controller (the model you ordered)

 ..............................

x1

• Set of Brackets ........................................................................................

x1

• Unit Label (L4502VZ)

 ..............................................................................

x1

• Tag Label (L4502VE)

 ..............................................................................

x1

  (Only when ordered.)

• Operation Guide (this document)

 ............................................................

x5 (A3 size)

  (Installation and Wiring, Initial Settings, Operations, and Parameters)

Target Readers

This guide is intended for the following personnel;

•  Engineers responsible for installation, wiring, and maintenance of the equipment.

•  Personnel responsible for normal daily operation of the equipment.

1.  Safety Precautions

The following symbol is used on the instrument. It indicates the possibility of injury 

to the user or damage to the instrument, and signifies that the user must refer to the 

operation guide or user’s manual for special instructions. The same symbol is used in 

the operation guide and user’s manual on pages that the user needs to refer to, together 

with the term “WARNING” or “CAUTION.”

WARNING 

Calls attention to actions or conditions that could cause serious 

or fatal injury to the user, and indicates precautions that should be 

taken to prevent such occurrences.

CAUTION

Calls attention to actions or conditions that could cause injury to 

the user or damage to the instrument or property and indicates pre-

cautions that should be taken to prevent such occurrences.

AC

AC/DC

 

The equipment wholly protected by double insulation or reinforced insulation.

  

Functional grounding terminals 

   

(Do not use this terminal as a protective grounding terminal).

Note

Identifies important information required to operate the instrument.

  Warning and Disclaimer

(1) YOKOGAWA makes no warranties regarding the product except those stated in 

the WARRANTY that is provided separately.

(2) The product is provided on an "as is" basis. YOKOGAWA assumes no liability to 

any person or entity for any loss or damage, direct or indirect, arising from the 

use of the product or from any unpredictable defect of the product.

■  Safety, Protection, and Modification of the Product

(1) In order to protect the system controlled by this product and the product itself, 

and to ensure safe operation, observe the safety precautions described in the 

operation guide. Use of the instrument in a manner not prescribed herein may 

compromise the product's functions and the protection features inherent in the 

device. We assume no liability for safety, or responsibility for the product's quality, 

performance or functionality should users fail to observe these instructions when 

operating the product.

(2) Installation  of protection  and/or safety circuits with respect to a lightning 

protector; protective equipment for the system controlled by the product and the 

product itself; foolproof or fail-safe design of a process or line using the system 

controlled by the product or the product itself; and/or the design and installation 

of other protective and safety circuits are to be appropriately implemented as the 

customer deems necessary.

(3) Be sure to use the spare parts approved by YOKOGAWA when replacing parts 

or consumables.

(4) This product is not designed or manufactured to be used in critical applications 

that directly affect or threaten human lives. Such applications include nuclear 

power  equipment,  devices  using  radioactivity,  railway  facilities,  aviation 

equipment, air navigation facilities, aviation facilities, and medical equipment. 

If so used, it is the user’s responsibility to include in the system additional 

equipment and devices that ensure personnel safety.

(5) Modification of the product is strictly prohibited.

(6) This product is intended to be handled by skilled/trained personnel for electric devices.

(7) This product is UL Recognized Component. In order to comply with UL standards, 

end-products are necessary to be designed by those who have knowledge of the 

requirements.

WARNING 

Power Supply

  Ensure that the instrument’s supply voltage matches the voltage 

of the power supply before turning ON the power.

l

  Do Not Use in an Explosive Atmosphere

  Do not operate the instrument in locations with combustible 

or explosive gases or steam. Operation in such environments 

constitutes an extreme safety hazard. Use of the instrument in 

environments with high concentrations of corrosive gas (H

2

S, 

SO

X

, etc.) for extended periods of time may cause a failure.

l

  Do Not Remove Internal Unit

  The internal unit should not be removed by anyone other than 

YOKOGAWA's service personnel. There are dangerous high voltage 

parts inside. Additionally, do not replace the fuse by yourself.

l

  Damage to the Protective Construction

  Operation of the instrument in a manner not specified in the 

operation guide may damage its protective construction.

CAUTION

This instrument is an EMC class A product. In a domestic environ-

ment this product may cause radio interference in which case the 

user needs to take adequate measures.

2.  Model and Suffix Codes

  UT32A «Entry Model»

Model

Suffix code

Option 

code

Description

UT32A

Digital Indicating Controller (Power supply: 100-240 V 

AC) (provided with 2 DOs) 

Type 1: 

Basic 

control

-V

Voltage pulse output type

-C

Current output type

-R

Relay output type

Type 2: 

Functions

0

None

1

RS-485 communication (Max. 38.4 kbps, 2-wire/4-wire) (*1)

Type 3: Fixed code

0

None

Display language (*2)

-1

English (Default. Can be switched to other language by the setting.)

-2

German (Default. Can be switched to other language by the setting.)

-3

French (Default. Can be switched to other language by the setting.)

-4

Spanish (Default. Can be switched to other language by the setting.)

Case color

0

White (Light gray)

1

Black (Light charcoal gray)

Fixed code

-00

Always "-00" (for Standard Code Model)

Option codes

/LP

24 V DC loop power supply

/DC

Power supply 24 V AC/DC

/CT

Coating (*3)

/CV

Terminal cover

*1:  When the /LP option is specified, the RS-485 communication of the Type 2 code “1” is 2-wire 

system.

*2:  English, German, French, and Spanish are available for the guide display.

*3:  When the /CT option is specified, the UT32A does not conform to the safety standards (UL 

and CSA) and CE marking (Products with /CT option are not intended for EEA-market).

■ Customized Product

  For customized product, the product is identified by the option code of /S# (where ‘#’ 

is a number).

  Contact your supplier in case your instrument has option /S#, and you are not 

in the possession of FX1-[Model code]-S# or IM [Model code]-S# (where [Model 

code] means, for example, UT55A).

  Accessories (sold separately)

The following is an accessory sold separately.

•  LL50A Parameter Setting Software

Model

Suffix code

Description

LL50A

-00

Parameter Setting Software

•  External Precision Resistor 

Model

Suffix code

Description

X010

See the General Specifications (*) Resistance Module

 

*: Necessary to input the current signal to the voltage input terminal.

•  Terminal Cover: Model UTAP002

• Manuals

 

Note: Manuals can be downloaded from a website. URL: http://www.yokogawa.com/ns/ut/im/

• Brackets

  Part number: L4502TP (2 pcs for upper and lower sides)

3.  How to Install

  Installation Location

The instrument should be installed in indoor locations meeting the following 

conditions:

•  Instrumented panel

  This instrument is designed to be mounted in an instrumented panel. Mount the 

instrument in a location where its terminals will not inadvertently be touched.

•  Well ventilated locations

  Mount the instrument in well ventilated locations to prevent the instrument’s inter-

nal temperature from rising. 

  However, make sure that the terminal portions are not exposed to wind. Exposure 

to wind may cause the temperature sensor accuracy to deteriorate. To mount mul

-

tiple indicating controllers, see the external dimensions/panel cutout dimensions 

which follow. 

If mounting other instruments adjacent to the instrument, comply with 

these panel cutout dimensions to provide sufficient clearance between the instruments.

•  Locations with little mechanical vibration

  Install the instrument in a location subject to little mechanical vibration.

•  Horizontal location

  Mount the instrument horizontally and ensure that it is level, with no inclination to 

the right or left.

Front panel

of controller

Keep this angle

within 30°

Rear of

controller

30°

Note

If the instrument is moved from a location with low temperature and low humidity 

to a place with high temperature and high humidity, or if the temperature changes 

rapidly, condensation will result. Moreover, in the case of thermocouple inputs, 

measurement errors will result. To avoid such a situation, leave the instrument in the 

new environment under ambient conditions for more than 1 hour prior to using it.

Do not mount the instrument in the following locations:

• Outdoors

•  Locations subject to direct sunlight or close to a heater

  Install the instrument in a location with stable temperatures that remain close to an 

average temperature of 23°C. Do not mount it in locations subject to direct sunlight 

or close to a heater. Doing so adversely affects the instrument.

• Locations with substantial amounts of oily fumes, steam, moisture, dust, or 

corrosive gases

  The presence of oily fumes, steam, moisture, dust, or corrosive gases adversely 

affects the instrument. Do not mount the instrument in locations subject to any of 

these substances.

•  Areas near electromagnetic field generating sources

  Do not place magnets or tools that generate magnetism near the instrument. If the 

instrument is used in locations close to a strong electromagnetic field generating 

source, the magnetic field may cause measurement errors.

•  Locations where the display is difficult to see

  The instrument uses an LCD for the display unit, and this can be difficult to see 

from extremely oblique angles. Mount the instrument in a location where it can be 

seen as much as possible from the front.

•  Areas close to flammable articles

  Absolutely do not place the instrument directly on flam-

mable surfaces. If such a circumstance is unavoidable 

and the instrument must be placed close to a flammable 

item, provide a shield for it made of 1.43 mm thick plated 

steel or 1.6 mm thick unplated steel with a space of at 

least 150 mm between it and the instrument on the top, 

bottom, and sides.

•  Areas subject to being splashed with water

WARNING 

Be sure to turn OFF the power supply to the controller before in-

stalling it on the panel to avoid an electric shock.

150 mm

150 mm

150 mm

150 mm

Operation

Guide

IM 05P01F31-11EN

UT32A-V , -C, -R

Digital Indicating Controller

 

Operation Guide

This operation guide describes installation, wiring, and other tasks required to make the 

controller ready for operation.

3rd Edition : Mar. 2018

Installation and Wiring

For details of the each function, refer to the electronic manual. Manuals can be 

downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

«Entry Model»

www.yokogawa.com/ns

YOKOGAWA ELECTRIC CORPORATION

Network Solutions Business Division

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPAN

YOKOGAWA CORPORATION OF AMERICA

Head office and for product sales

2 Dart Road, Newnan, Georgia 30265, USA

YOKOGAWA EUROPE B.V.

Headquarters

Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS

All Rights Reserved, Copyright © 2015 Yokogawa Electric Corporation

•  Authorised Representative in the EEA

  Yokogawa Europe BV. (Address: Euroweg 2 , 3825 HD Amersfoort, The Nether-

lands) is the Authorised Representative of Yokogawa Electric Corporation for this 

Product in the EEA.

•  Printed Manuals

Model

Description

UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide 

«

Standard Code Model

»

IM 05P01D31-11EN

UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide 

«

Detailed Code Model

»

IM 05P01D31-15EN

UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) 

Operation Guide 

«

Standard Code Model

»

IM 05P01D81-11EN

UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type) 

Operation Guide 

«

Standard Code Model

»

IM 05P08D31-11EN

UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) 

Operation Guide 

«

Standard Code Model

»

IM 05P08D81-11EN

UT35A/RSP, UT32A/RSP Digital Indicating Controller (Non-isolated Remote 

Input, Panel Mounting Type) Operation Guide 

«

Standard Code Model

»

IM 05P01D31-81EN

UT32A Digital Indicating Controller Operation Guide 

«

Entry Model

»

IM 05P01F31-11EN

Precautions on the Use of the UTAdvanced Series

IM 05P01A01-11EN

•  Electronic Manuals

  You can download the latest manuals from the following website:

  URL: http://www.yokogawa.com/ns/ut/im/

Model

Description

UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide 

«

Standard Code Model

»

IM 05P01D31-11EN

UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide 

«

Detailed Code Model

»

IM 05P01D31-15EN

UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) 

Operation Guide 

«

Standard Code Model

»

IM 05P01D81-11EN

UT35A/UT32A Digital Indicating Controller User’s Manual

IM 05P01D31-01EN

UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type) 

Operation Guide 

«

Standard Code Model

»

IM 05P08D31-11EN

UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) 

Operation Guide 

«

Standard Code Model

»

IM 05P08D81-11EN

UT32A-D, UT32A-D/MDL Digital Indicating Controller User’s Manual

IM 05P08D31-01EN

UT35A/RSP, UT32A/RSP Digital Indicating Controller (Non-isolated Remote 

Input, Panel Mounting Type) Operation Guide 

«

Standard Code Model

»

IM 05P01D31-81EN

UT32A Digital Indicating Controller Operation Guide 

«

Entry Model

»

IM 05P01F31-11EN

UT32A Digital Indicating Controller User’s Manual 

«

Entry Model

»

IM 05P01F31-01EN

UTAdvanced Series Communication Interface (RS-485, Ethernet) User’s Manual IM 05P07A01-01EN
UTAdvanced Series Communication Interface (Open Network) User’s Manual

IM 05P07A01-02EN

LL50A Parameter Setting Software Installation Manual

IM 05P05A01-01EN

LL50A Parameter Setting Software User’s Manual

IM 05P05A01-02EN

Precautions on the Use of the UTAdvanced Series

IM 05P01A01-11EN

•  General Specification

Model

Description

UT35A, UT32A Digital Indicating Controller (Panel Mounting Type)

GS 05P01D31-01EN

UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) GS 05P01D81-01EN
UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type)

GS 05P08D31-01EN

UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) GS 05P08D81-01EN
LL50A Parameter Setting Software

GS 05P05A01-01EN

The last two characters of the manual number and general specification number indicate the 

language in which the manual is written.

 

Protection of Environment

  Waste Electrical and Electronic Equipment (WEEE), Directive

This is an explanation of how to dispose of this product based on Waste Electrical 

and Electronic Equipment (WEEE), Directive. This directive is only valid in the EU.

●  Marking

This  product  complies  with  the  WEEE  Directive  marking 

requirement. This marking indicates that you must not discard 

this electrical/electronic product in domestic household waste.

●  Product Category

With reference to the equipment types in the WEEE directive, 

this product is classified as a “Small equipment” product.
Do not dispose in domestic household waste. When disposing 

products in the EU, contact your local Yokogawa Europe B.V. 

office.

Summary of Contents for UT32A-C

Page 1: ...umented panel Mount the instrument in a location where its terminals will not inadvertently be touched Well ventilated locations Mount the instrument in well ventilated locations to prevent the instru...

Page 2: ...e set manually Reference junction compensation error 1 0 C 15 to 35 C 1 5 C 10 to 15 C and 35 to 50 C Applicable standards JIS IEC DIN ITS 90 for TC and RTD Analog Output Specifications Suffix code C...

Page 3: ...urrent as a spark removal surge suppression circuit into the line in parallel with the load After completing the wiring the terminal cover is recommended to use for the instrument Recommended Crimp on...

Page 4: ...IM 05P01F31 11EN page 4 10 Intentionally blank Intentionally blank...

Page 5: ...to easily set the basic function of the controller Turn on the controller to start the Quick setting function This function allows you to easily set the control type and input and quickly start the c...

Page 6: ...nt Open unlit SP or Target SP Alarm setpoint Hysteresis SP or Target SP Hysteresis Alarm setpoint Alarm setpoint Output Hysteresis Closed lit Hysteresis Alarm setpoint Output Alarm setpoint Hysteresis...

Page 7: ...arrow keys to display the required setpoint Blinks during the change The setpoint has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see U...

Page 8: ...Contact us for repair ERR SYS System data error System data is corrupted Faulty Contact us for repair PAR 0004 for user default value error only Setup parameter PA ER User parameter default value erro...

Page 9: ...13 Target SP deviation high and low limits 14 Target SP deviation within high and low limits 15 OUT high limit 16 OUT low limit 19 Analog input PV high limit 20 Analog input PV low limit 29 PV velocit...

Page 10: ...Ladder communication CO M Coordinated master station CO S Coordinated slave station MBASC Modbus ASCII MBRTU Modbus RTU CO S1 Coordinated slave station Loop 1 mode CO S2 Coordinated slave station Loo...