123
Refrigeration Service Operations
NOTE: It is generally good practice to replace
the filter-drier whenever the high side is opened
or when the low side is opened for an extended
period of time.
Commissioning Unit
The following procedure should be followed after
any of these conditions:
•
The compressor has been replaced
•
There has been a large oil loss in the system
•
There has been a complete clean up or flush of
the refrigeration system.
1. Set the thermostat to the highest setpoint.
2. Run the unit for ten minutes to allow for
wetting of the system.
3. Set the thermostat for Cool (remove jumpers if
installed in the previous step).
Low Side Pump Down
NOTE: Operate the unit in COOL for 2 to 5
minutes before performing the low side pump
down.
1. Unplug the hot gas bypass solenoid.
2. Install a gauge manifold to the suction service
valve and the discharge service port.
3. Operate the unit in low speed cool.
4. Close the receiver tank outlet valve and allow
the low side to pump down to 0 to 5 in. Hg
vacuum (0 to -17 kPa).
5. Turn the unit Off.
6. Prepare to perform service on the low side by
equalizing the high side and low side
pressures through the gauge manifold.
7. Equalize low side pressure to 1 to 2 psig (7 to
14 kPa).
NOTE: Repeat the pump down procedure if
the pressures equalize above 20 psig
(138 kPa). If acceptable low pressures
cannot be achieved after the third pump
down, the refrigerant must be recovered to
perform service on the low side.
NOTE: Valve stem MUST be back seated
during normal unit operation.
8. Plug in the hot gas bypass solenoid.
9. Open the receiver tank return outlet valve,
remove the gauges and return the unit to
normal operation.
Accumulator
Removal
1. Remove refrigerant using approved methods.
2. Unsolder the inlet and outlet refrigerant
suction lines from the accumulator tank.
3. Unbolt and remove the accumulator from the
unit.
Installation
1. Place the accumulator in the unit and tighten
the mounting bolts.
2. Solder the inlet and outlet suction lines to the
accumulator tank.
3. Pressurize the low side and test for refrigerant
leaks. If no leaks are found, evacuate unit.
4. Charge the system with refrigerant. Check
refrigerant charge and compressor oil and add
as required.
Summary of Contents for 914970
Page 3: ...3...
Page 10: ...Table of Contents 10...
Page 40: ...Operating Instructions 40...
Page 82: ...Electronic Controls 82...
Page 92: ...Electrical Maintenance 92...
Page 124: ...Refrigeration Maintenance 124...
Page 140: ...Hilliard Clutch Maintenance 140...
Page 160: ...Refrigeration Diagrams 160...
Page 163: ...Index 163 W wiring 85 wiring diagrams 165...
Page 164: ...Index 164...
Page 166: ...Wiring and Schematic Diagrams Index 166...
Page 167: ...167 Cab Control RD Wiring Diagram...
Page 168: ...168 RD w o Thermostat Cab Control Schematic...
Page 169: ...169 RD Cab Box Wiring Diagram...
Page 170: ...170 RD Cab Control w Thermostat Schematic Diagram...
Page 171: ...171 RD 50 STD 3 Phase Wiring Diagram Page 1 of 2...
Page 172: ...172 RD 50 STD 3 Phase Wiring Diagram Page 2 of 2...
Page 173: ...173 RD 50 STD 3 Phase Schematic Diagram Page 1 of 2...
Page 174: ...174 RD 50 STD 3 Phase Schematic Diagram Page 2 of 2...
Page 175: ...175 RD 30 STD Wiring Diagram Page 1 of 2...
Page 176: ...176 RD 30 STD Wiring Diagram Page 2 of 2...
Page 177: ...177 RD 30 STD Schematic Diagram Page 1 of 2...
Page 178: ...178 RD 30 STD Schematic Diagram Page 2 of 2...
Page 179: ...179 RD 30 C S Wiring Diagram Page 1 of 2...
Page 180: ...180 RD 30 C S Wiring Diagram Page 2 of 2...
Page 181: ...181 RD w CYCLE SENTRY Schematic Diagram Page 1 of 2...
Page 182: ...182 RD w CYCLE SENTRY Schematic Diagram Page 2 of 2...
Page 183: ...183 RD 50 C S 3 Phase Wiring Diagram Page 1 of 2...
Page 184: ...184 RD 50 C S 3 Phase Wiring Diagram Page 2 of 2...
Page 185: ...185 RD w CYCLE SENTRY Schematic Diagram Page 1 of 2...
Page 186: ...186 RD w CYCLE SENTRY Schematic Diagram Page 2 of 2...