50
C.
PERIODIC MAINTENANCE RECOMMENDED CHECK LIST
Frequency
Component/Item
Recommended Test
Daily
Maintenance
Boiler surroundings
Inspect the area to assure proper clearance to combustible materials,
gasoline, and other flammable vapors and liquids.
Gauges, monitors, and indicators
Make visual inspection and record readings.
Combustion Properties
Check combustion properties as specified in section VII, part D.
Burner flame
Make visual inspection of burner flame as stated in section VII, part D.
Low Draft, fan air pressure, and damper
position interlocks
Test low draft, fan, air pressure, and damper position interlocks
according to instructions if so equipped.
Weekly
Maintenance
Igniter
Make visual inspection, check flame signal strength; log.
Flame signal strength
Read and log flame signal meter, read for both pilot and main flames.
Flame failure detection system
Close manual fuel supply for (1) pilot, (2) main fuel cock, and/or
valve(s); check safety shutdown timing. Refer to section VII, Part D.
Firing rate control
Check firing rate control, place RWF 40 in manual mode and check
high and low firing settings for proper operation.
Pilot and/or main fuel valves
Open limit switch and make aural and visual check; check valve
position indicators and check fuel meters if so fitted.
Low-water fuel cutoff
Test low-water fuel cutoff device and alarm according to
manufacturer’s instructions.
Monthly
Maintenance
Flue, vent, stack, condensate drains,
and outlet dampers
Confirm that components are gas tight and free from obstructions to
flow.
Gas pressure interlocks
Test high and low gas pressure interlocks.
Water condition
Test condition of water, correct condition as needed.
Semi-Annual
Maintenance
Gauges, monitors, and indicators
Recalibrate all indicating and recording gauges.
Flame failure detection system
Check components.
Condensate drain tubes
Check drain tubes have liquid in trap and condensate is properly
directed.
Air filter
Check air filter as specified in section VII, Part D.
Interlocks and valves
Check piping and wiring of all interlocks and shut off valves if so
equipped.
Circulators and system pumps
Maintain according to manufacturers' instructions.
Annual
Maintenance
Flue, vent, stack, or outlet dampers
Confirm that components are gas tight and free from obstructions to
flow.
Combustion Properties
Check combustion properties as specified in section IV, Part I, Step 5.
Flame failure detection system
Conduct pilot turndown test according to manufacturer’s instructions.
This test is required annually and after any adjustments to flame
scanner mount or pilot burner.
Pilot and/or main fuel valves
Check all coils and diaphragms; test other operating parts of all safety
shutoff and control valves.
Pilot and/or main fuel valves
Perform leakage test on pilot and main gas and/or oil fuel valves, in
accordance with instructions.
Flame safeguard
Test purge timing according to manufacturer’s instructions.
Air Filter
Replace.
Boiler trim
Remove lower front jacket panel and check for any signs of corrosion
and leaks.
High limit and operating temp. controls
Test proper operation.
As-Required
Low-water fuel cutoff
Recondition or replace.
Safety relief valves
Test safety relief valves in accordance with ASME Boiler and Pressure
Vessel Code, Sections VI and VII.
Summary of Contents for EVO-1000
Page 13: ...13 Figure 4 Vertical Pressurized Venting...
Page 15: ...15 Figure 5 Typical Negative Pressure Conventional Venting...
Page 17: ...17 Figure 7 Vertical Air Intake Piping...
Page 26: ...26 Figure 9a Standard UL FM CSD 1 Wiring Diagram on off EVO 500 2000...
Page 27: ...27 Figure 9b Standard UL FM CSD 1 Wiring Diagram Modulation EVO 500 2000...
Page 30: ...30 Figure 11 Modular System Horizontal Air Intake Piping...
Page 31: ...31 Figure 12 Modular System Vertical Air Intake Piping...
Page 32: ...32 Figure 13 Modular System Typical One Pipe Water Piping...
Page 33: ...33 Figure 14 Modular System Typical Primary Secondary Water Piping...
Page 34: ...34 Figure 15 Modular System Typical Primary Secondary without System Pump...
Page 35: ...35 Figure 16 Modular System Typical Reverse Return Water Piping...
Page 36: ...36 Figure 17 Modular System Reverse Return with System Pump Only...
Page 37: ...37 Figure 18 Modular System Typical Primary Secondary with Reverse Return...
Page 47: ...47 This Page Intentionally Left Blank...
Page 48: ...48 Troubleshooting Guide B Troubleshooting Guide...
Page 49: ...49 Troubleshooting Guide...
Page 53: ...53 This Page Intentionally Left Blank...
Page 54: ...54 Figure 19 Combustion Chamber Assembly...
Page 56: ...56 Figure 20 Burner Assembly FRONT VIEW TOP VIEW...
Page 58: ...58 Figure 21 UL FM CSD 1 Main Gas Train Assembly...
Page 60: ...60 Figure 22a DB B DB B w POC Gas Train 500 750 Figure 22b DB B DB B w POC Gas Train 1000 2000...
Page 62: ...62 Figure 23 Jacket Panels 4D 4J 4C 4B 4F 4I 4G 4E 4R 4K 4H 4J 4N 4M 4L 4Q 4A 4P 4P...
Page 64: ...64 Figure 24a Control Panel Assembly On Off...
Page 66: ...66 Figure 24b Control Panel Assembly Modulation...
Page 68: ...68 Figure 25 Bishop Pilot Assembly...
Page 72: ...72 NOTES...
Page 73: ...73 NOTES...
Page 74: ...74 NOTES...
Page 75: ...75 NOTES...