Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
77
of
89
6.7 Determining the current operating mode
The current setpoint can be adjusted to the relevant requirements via the choice of operating
mode.
The operating mode can be set via objects 21...23.
For this, there are two methods:
6.7.1 New operating modes
If New... is selected in the "Determination of operating mode" parameter on the "Operating
mode" parameter page, the current operating mode can be defined as follows:
Table 62
Operating mode
preset
Object 21
Presence
Object 22
Window status
Object 23
current operating
mode
(object 24)
any
any
1
Frost/heat protection
any
1
0
Comfort
Comfort
0
0
Comfort
Standby
0
0
Standby
Night
0
0
Night
Frost/heat protection
0
0
Frost/heat protection
Typical application:
In the mornings, object 21 activates "Standby" or "Comfort", and "Night" in the evenings via a
time switch (e.g. TR 648).
During holiday periods, frost/heat protection is selected via another channel of the time switch,
also via object 21. Object 22 is connected to a presence detector. If presence is detected,
FCA 2 switches to comfort operating mode (see table).
Object 23 is connected to a window contact via the bus (binary input).
As soon as a window is opened, FCA 2 switches to frost protection operating mode.
Operating mode
Specification
Frost
protection
Night
Presence
Standby
0
Window
Comfort
0
1
Current
Operating
mode
Comfort
1
Frost
protection
Figure 12