Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
16
of
89
•
Object 8 "Fan stage in forced operation"
Via this object, the desired fan stage in forced operation is either defined as a percentage value
between 0 % and 100 % or as a stage (1-3).
See parameter
Format of forced operation and limitation
on
Fan
parameter page.
With 0-10 V fan control, only the percentage value format is permitted.
The specification fan stage can either be made with the button at the room thermostat
RAM 713 FC or via a KNX sensor (e.g. push button), which is configured for this purpose.
Forced operation is activated by Object 15.
Example of percentage value:
Recommended forced telegrams for the following settings on the
"Fan"
parameter page:
Switch-on threshold for fan stage 1
= 10 %
Switch-on threshold for fan stage 2
= 40 %
Switch-on threshold for fan stage 3
= 70 %
Forced-operation telegram
Forced-operation telegram
Forced-operation telegram
25 %
55 %
85 %
STAGE 1
STAGE 2
STAGE 3
10 %
40 %
70 %
100 %
Switch-on thresholds
Figure 2