Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
37
of
89
3.4.6 Parameter page Additional relay
Table 25
Designation
Values
Meaning
Switching on the additional
relay
Via object
The additional relay is only
controlled from outside via
the bus (see object 5)
If heating is required
The additional relay is
switched on as soon as the
heating actuating value is
above 0 %.
If cooling is required
The additional relay is
switched on as soon as the
cooling actuating value is
above 0 %.
Combined with heating valve
The additional relay only
switches on when the heating
valve is actually opened*.
Combined with cooling valve
The additional relay only
switches on when the cooling
valve is actually opened*.
Transmission of additional
relay status every
do not send cyclically
3 min
5 min
10 min
15 min
20 min
30 min
60 min
Cyclical transmission time for
the additional relay status.
With the setting
Switching on
the additional relay=
via object
, the status is not
transmitted.
* With an adjusted valve characteristic, the valve can remain closed with a low actuating value.