Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
67
of
89
5.4.5 Important parameter settings
The standard parameter settings apply for unlisted parameters.
Table 54: FCA 2
Parameter page
Parameters
Setting
General
Supported function
Heating and cooling
Heating system
Fan coil
Cooling system
Fan coil
Installation type
4-pipe system
Type of controller used
external controller
Setpoint adjustment
Setpoint correction from
25 °C
Adjustment
1 K per 3 K outdoor temperature
Format of correction value
relative
Table 55: RAM 713 FC
Parameter page
Parameters
Setting
Settings
Device type
RAM 713 Fan Coil
Operation
Rotary control function
Manual adjustment with report
object
Control
Fan coil system used
4-pipe system
Changeover between heating and
cooling
Automatic
Operating mode
Objects for determining the
operating mode
new: operating mode, presence,
window status
Table 56: Meteodata 140 S
Parameter page
Parameters
Setting
Measurement values
Send temperature in the event of
change
From 1.0 °C
Table 57: TR 648 top 2 RC KNX time switch
Parameter page
Parameters
Setting
General
Activate time switch channel C1
Valuator
Switching channel
C1
Telegram type C1.1
HVAC operating mode
With clock
ON
Send following telegram once
Telegram
Standby
With clock
OFF
Send following telegram once
Telegram
Temperature reduction at night