Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
41
of
89
Continuation:
Designation
Values
Meaning
Format of correction value relative
Obj. 19 sends a temperature
difference in K, depending on
the outdoor temperature.
This value can be used as a
setpoint offset for additional
room thermostats.
absolute
Obj. 19 sends a setpoint in °C
(
base unadjusted setpoint
).
This is increased step-by-step
depending on the outdoor
temperature and serves as
setpoint for additional
temperature controllers.
Unadjusted base setpoint
15 °C, 16 °C, 17 °C
18 °C, 19 °C, 20 °C
21 °C, 22 °C, 23 °C
24 °C, 25 °C, 26 °C,
27 °C , 28 °C
29 °C, 30 °C
Base setpoint for additional
room thermostats.
Important:
This value should match with
the base setpoint of the
actuated controller.
Transmission of setpoint
correction every
do not send cyclically
3 min, 5 min, 10 min, 15 min
20 min, 30 min,
60 min
Cyclical transmission time for
setpoint correction.