Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
12
of
89
Continuation:
No.
Function
Object name
Type
C R W T
21
Night mode <-> Standby
1 = Night mode
1 bit
1,001
C R W -
Operating mode preset
Operating mode preset
1 byte
20,102
C R W -
22
Comfort
1 = Comfort mode
1 bit
1,001
C R W -
Presence
Input for presence signal
1 bit
1,018
C R W -
23
Frost protection
1 = Frost protection
1 bit
1,001
C R W -
Window
Input for window contact
1 bit
1,019
C R W -
24
Current operating mode
Send
1 byte
20,102
C R - T
25
Manual offset
Receive
2 byte
9,002
C R W -
26
Base setpoint
Receive
2 byte
9,001
C R W -
27
Current setpoint
Send
2 byte
9,001
C R - T
28
Heating / cooling
Heating = 0, Cooling = 1
1 bit
1,001
C R W -
Heating / cooling
Heating = 1, Cooling = 0
1 bit
1,100
C R W -
29
No energy medium
1 = Wrong energy medium
1 bit
1,001
C R - T
Heating mode, but heating
blocked
1 = Heating blocked
Cooling mode, but cooling
blocked
1 = Cooling blocked
30
Fan duty time since last filter
change
Time in hours
2 byte
7,007
C R - T
31
Change filter*
1 = Change, 0 = Reset
1 bit
1,001
C R W T
32
Activate test mode
Report
1 bit
1,003
C R - T
* Also serves as reset input for filter change status.
Key
Flags Name
Meaning
C
Communication Object can communicate
R
Read
Object status can be queried
W
Write
Object can receive
T
Transmit
Object can send