Automatic boiler for wood pellets
63
Error states
9.4
ERROR - OVERHEATING, EMERGENCY THERMOSTAT
The control unit is equipped with emergency circuit in case of overheating of the boiler. OVERHEATING fault
condition occurs when the water temperature at the outlet exceeds a threshold of 95 ° C. In this situation, the
emergency circuit is activated by the control unit and the boiler is shut down.
This is indicated by the lighting up of this red box:
Only circulating pump is put into operation for heat dissipation of the heat exchanger.
Under normal circumstances, there is no overheating of the boiler, so this condition is considered an emergency.
It requires operator intervention (service), which must evaluate why this situation occurred.
Possible causes
Elimination
Performed by
The boiler water temperature is
set to a high value
(around 90 ° C)
Reduce output water temperature (Menu 2) to f.e.
80 ° C.
user
Insufficient heat dissipation from
the boiler
- circulation pump not running
Control of the circulation pump, or switching to
higher power.
user
- blocked cleaning strainer
Close the valves and clean the strainer.
installer
- wrong hydraulice of heating
circuit (all thermoheads
closed)
Check the temperature during Stand – by mode and
set a longer period of time
installer
Too short Stand - by time of the
boiler without electric ignition
ExtendStand – by parameter (in the Menu Service)
service
Larger amount of unburned
pellets in the combustion
chamber
Carefully clean the burner chamber and
professionally set the combustion.
service
Summary of Contents for KP 12-ES
Page 21: ...Automatic boiler for wood pellets 20 Picture No 15 Jacketing KP 22S KP 22 ES ...
Page 22: ...Automatic boiler for wood pellets 21 Picture No 16 Jacketing KP 62S KP 62 ES ...
Page 43: ...Automatic boiler for wood pellets 42 9 3 1 2Menu users settings ...
Page 45: ...Automatic boiler for wood pellets 44 Cleaning an ash removeing Skin Time window setting ...
Page 48: ...Automatic boiler for wood pellets 47 Actual values Configuration ...
Page 54: ...Automatic boiler for wood pellets 53 Cleaning Ash removing USB Time window setting ...
Page 55: ...Automatic boiler for wood pellets 54 Load from USB Save on USB ...
Page 60: ...Automatic boiler for wood pellets 59 ...
Page 62: ...Automatic boiler for wood pellets 61 ...
Page 63: ...Automatic boiler for wood pellets 62 i ...
Page 70: ...69 Picture No 31 Principle of the modulation ...
Page 72: ...71 Picture No 33 Directory information consuption wood pellets for boiler family KP ...
Page 73: ...72 Picture No 34 Circuit diagram control unit ...
Page 74: ...73 Picture No 35 Circuit diagram modul HZS 533 ...
Page 75: ...74 Picture No 36 Circuit diagram HZS 533 HZS 535 ...