4
www.tescom-ups.gr
NEOLINE
PRO
�
1/1
�
1-3 kVA
�
ONLINE UPS
USER MANUAL
4
Charger output voltage 27.1± 0.4
40.6± 0.6
54.2± 0.8
81.3
± 1.2
81.3
± 1.2
Recharging time
Standard model: 90% capacity restored in 3 hours;
Long time model: depend on the capacity of battery
Charging current
(Max.)
Standard model: 1 A
System Control and Communications
Protections
Over-temp protection; Fan testing protection; Overload protection;
Output short circuit protection; Battery discharge protection
Communication port
Standard: RS232; Options: USB, SNMP card, dry contacts
Display
LCD+LED
Environmental
Operatinghumidity
0 ~ 95 % RH @ 0 ~ 40°C (non-condensing)
Storage temperature
-25°C ~ 55°C(exclude batteries)
Operating altitude
≤ 1000m, above 1000m, derate 1% for each rising 100m
Protection class
IP20
Noise level
≤50dB (at 1m)
Others
Dimensions (mm)
W × D × H
440*316*88 440*430*88 440*430*88 440*560*88
440*560*88
Weight (kg)
10.6
15.5
18.7
25.6
26.8
* Derate capacity to 70% in CUCF mode and to 90% when the output voltage is adjusted to 208Vac.
Note
:
:
2.2 Front panel features
Model
Type
1kVASRT
1 kVA Standard model
2kVASRT
2 kVA Standard model
3kVASRT
3 kVA Standard model