11
NEOLINE
PRO
�
1/1
�
1-3 kVA
�
ONLINE UPS
USER MANUAL
11
Position
Definition
PIN1
ON
:
UPS is malfunctioning
PIN2
ON
:
Alarm
(
system failure
)
PIN3
Ground
PIN4
Remote shutdown
PIN5
Common
PIN6
ON
:
Bypass mode
PIN7
ON
:
Battery low
PIN8
ON
:
Inverter mode
;
OFF
:
Bypass mode
PIN9
ON
:
No AC power in
5 Operation
5.1 Button operation
Button
Function
“ON” key
(
+
)
Press the two keys for more than half a second to turn on the UPS.
“OFF” key
(
+
)
Press the two keys for more than half a second to turn off the UPS.
TEST/MUTE key
(
+
)
Press the two keys for more than 1 second in Line mode or ECO mode or
CUCF mode: UPS runs the self-test function.
Press the two keys for more than 1 second in battery mode: UPS runs the
mute function.
11
Position
Definition
PIN1
ON
:
UPS is malfunctioning
PIN2
ON
:
Alarm
(
system failure
)
PIN3
Ground
PIN4
Remote shutdown
PIN5
Common
PIN6
ON
:
Bypass mode
PIN7
ON
:
Battery low
PIN8
ON
:
Inverter mode
;
OFF
:
Bypass mode
PIN9
ON
:
No AC power in
5 Operation
5.1 Button operation
Button
Function
“ON” key
(
+
)
Press the two keys for more than half a second to turn on the UPS.
“OFF” key
(
+
)
Press the two keys for more than half a second to turn off the UPS.
TEST/MUTE key
(
+
)
Press the two keys for more than 1 second in Line mode or ECO mode or
CUCF mode: UPS runs the self-test function.
Press the two keys for more than 1 second in battery mode: UPS runs the
mute function.