NEOLINE
PRO
�
1/1
�
1-3 kVA
�
ONLINE UPS
USER MANUAL
16
LCD display
Setting
AUO setting only can be set in Stdby mode or Bypass
mode. You may choose the following two options:
ON
: UPS will start up automatically and works in Line mode
when connect mains.
OFF
(Default): UPS won’t start up automatically when
connect mains except EOD,it will work in standby or bypass
mode.
5.5 Parameters inquiring operation
Press the inquiring key
or
for more than half a second (less than 2 seconds)
to inquire about items. The inquired items include Input, Battery, Output, Load and
Temperature. The displayed items on LCD screen are shown as following:
LCD display
Description
Output
:
:
Display the output voltage and output frequency
of the UPS. As the following graphic shows, the output
voltage is 220V, the output frequency is 50Hz.
Load:
Display the numerical value of the active power
(WATT) and apparent power (VA) of the load. For example,
as the following graphics shows, the WATT of the load is
800W, VA is 1.0kVA (when disconnect loads, it is a normal
phenomenon to show a small numerical value of WATT and
VA).
Version and Temperature:
Indicate firmware version
ofUPSanddisplay the highest temperature of UPS
components; As the following graphics shows, the firmware
version is v1.7, the maximum temperature is 40
℃
.