Installation Manual
Type
:
MDR DIN rail power supply
(
Series
:
MDR-10, MDR-20, MDR-40, MDR-60, MDR-100
)
MDR-10-5
INPUT: 100 -240VAC 0.33A 50/60Hz
OUTPUT: 5V 2A
MDR-10-12
INPUT: 100 -240VAC 0.33A 50/60Hz
OUTPUT: 12V 0.84A
MDR-10-15
INPUT: 100 -240VAC 0.33A 50/60Hz
OUTPUT: 15V 0.67A
MDR-10-24
INPUT: 100 -240VAC 0.33A 50/60Hz
OUTPUT: 24V 0.42A
MDR-20-5
INPUT: 100 -240VAC 0.55A 50/60Hz
OUTPUT: 5V 3A
MDR-20-12
INPUT: 100 -240VAC 0.55A 50/60Hz
OUTPUT: 12V 1.67A
MDR-20-15
INPUT: 100 -240VAC 0.55A 50/60Hz
OUTPUT: 15V 1.34A
MDR-20-24
INPUT: 100 -240VAC 0.55A 50/60Hz
OUTPUT: 24V 1A
MDR-40-5
INPUT: 100 -240VAC 1.1A 50/60Hz
OUTPUT: 5V 6A
MDR-40-12
INPUT: 100 -240VAC 1.1A 50/60Hz
OUTPUT: 12V 3.33A
MDR-40-24
INPUT: 100 -240VAC 1.1A 50/60Hz
OUTPUT: 24V 1.7A
MDR-40-48
INPUT: 100 -240VAC 1.1A 50/60Hz
OUTPUT: 48V 0.83A
MDR-60-5
INPUT: 100 -240VAC 1.8A 50/60Hz
OUTPUT: 5V 10A
MDR-60-12
INPUT: 100 -240VAC 1.8A 50/60Hz
OUTPUT: 12V 5A
MDR-60-24
INPUT: 100 -240VAC 1.8A 50/60Hz
OUTPUT: 24V 2.5A
MDR-60-48
INPUT: 100 -240VAC 1.8A 50/60Hz
OUTPUT: 48V 1.25A
MDR-100-12
INPUT: 100 -240VAC 1.3A 50/60Hz
OUTPUT: 12V 7.5A
MDR-100-24
INPUT: 100 -240VAC 1.3A 50/60Hz
OUTPUT: 24V 4A
MDR-100-48
INPUT: 100 -240VAC 1.3A 50/60Hz
OUTPUT: 48V 2A
Introduction
MDR is a DIN rail power supply series with < 1W no load power consumption. And like other Mean Well’s DIN series,
they can be mounted on a TS35 Standard DIN rail.
Installation
(
1
)
Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a
heat source.
(
2
)
The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on
the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not
allowed.