KRB-5404
17
Table 3-2 D types
Frame size (A)
800
1250
1600
Type
AR208D
AR212D
AR216D
Max. rated current [
I
n
] (A) *1, *2
IEC, EN, AS
800
1250
1600
JIS
Marine use
N-phase rated current (A)
800
1250
1600
Number of poles *3, *4
3
4
3
4
3
4
Dielectric withstand voltage [
U
i
] (50/60Hz) *5
1000
1000
1000
Operating voltage [
U
e
] (50/60Hz) *6
690
690
690
Rated breaking/making current [kA sym rms]
IEC ,EN, AS [
I
CS
=
I
CU
]
JIS C 8201-2-1 Ann.1 Ann.2
AC 690V *8
42
AC 440V
50
For DC
DC 250V *10
40
Rated short-time current [
I
CW
] [kA rms] (1 sec.)
50
Endurance
in number of ON-
OFF cycles *11
Mechanical
With maintenance
26000
26000
26000
Without maintenance
12500
12500
12500
Electrical
Without
mainte-
nance
AC 460V
11000
11000
11000
Installation
Draw-out or fixed type
Mass (kg) for draw-out type
73
86
73
86
76
90
External dimensions (mm)
Fixed
type
*12
a
360
445
360
445
360
445
b
460
c
290
d
75
Draw-
out type
*13
a
354
439
354
439
354
439
b
460
c
345
d
40
Connection method
Line side
Vertical, horizontal or front terminals
Load side
Vertical, horizontal or front terminals
Control circuit terminal type
screw terminals
Spring charging method
Manual or motor charging
Overcurrent release (OCR)
No OCR, or L-characteristic for general feeder protection
(In case of AGR-11B)
No OCR, L-characteristic for general feeder protection,
R-characteristic for general feeder protection or
S-characteristic for generator protection (In case of
AGR-21B,22B,31B)
Operation indication
Group indication (In case of AGR-11B)
Individual indication (In case of AGR-21B,22B,31B)
Tripping device
Tripping coil
(TC)
Standard equipment for OCR-equipped ACB
Shunt trip device
(SHT)
Optional
undervoltage trip
device (UVT)
Optional
Auxiliary switches
Number of switches
4C (standard), 7C or 10C; available for general feeder or
microload
Terminal type
screw terminals
Operation power *14
Rated voltage
AC100, AC110V, AC120V, AC200V, AC220V, AC240V,
DC24V, DC48V, DC100V, DC110V, DC125V, DC200V or
DC220V
*1: Ambient temperature: 40°C (45°C for marine used)
)
*2: With horizontal terminals for AR208D
– 216D
*3: For 2-pole applications, use two poles at both ends.
*4: 4-pole ACBs are not applicable to power distribution IT systems unless N-phase protection is provided.
*5: Varies depending on applicable standards. AC1000V applies to ACBs conforming to IEC60947-2 and JIS C8201-2.
*6: Varies depending on applicable standards. AC690V applies to ACBs conforming to IEC60947-2 and JIS C8201-2.
*7: Applicable to 3-pole ACBs with INST or MCR.
*8: For applicability to power distribution IT systems, consult us
*10: A special version of the breaker is available to use above 250V DC. Contact Terasaki for details.
*11: Expected service life based on endurance test. The service life of ACB depends on the working and environmental conditions. Refer to chapter 6
“Maintenance, Inspection and
Parts Replacement
”.
*12: For both vertical and horizontal terminals
*13: This manual covers draw-out type ACBs.
*14:
For more information, please refer to page 23 and 25.