KRB-5404
107
Mounting the ACBs
Before mounting the ACBs check the type of interlock, number and length of the cables to ensure they are as ordered.
Install the ACBs (for fixed type) or chassis (for draw-out type) in the switchboard (see specifications section aformentioned
for dimensions).
When installing the ACBs, be sure to locate each ACB as you have specified (i.e. middle, left or right) when ordering.
A different arrangement does not permit correct installation of the interlock cables.
If the ACBs are draw-out types, do not insert the bodies into the chassis until the installation of the interlock system has
been complete. If the ACBs are fixed insure the ACBs are locked off during installation.
Cable Connections
The following illustration shows he connections between the ACBs.
Mounting the Cables
When installing the interlock cables, first perform the priority 1 connections and then priorty 2 in cable connections
chart above. Then follow the steps 1 to 10.
TYPE C.
TYPE A.
TYPE B.
TYPE D.
CABLE CONNECTION
Stamp
Cable
mounting
holes
Interlock Parts