KRB-5404
67
5-3-2-5-2. Reset screen(AGR-31B)
Fig. 62 shows how to navigate the reset screen and Table 32 lists the items that can be cleared on this screen. When an item is
cleared while its contact output is on, the contact output turns off.
Clear mode
Other settings can be
cleared in the same
way on the respective
subscreens.
: Flashing
Fig. 62 Reset screen navigation
Table 32 Reset subscreens
No.
Subscreen item
Description
○
1
(Monitor screen)
See 5-3-2-3-2.
○
2
Trip event log
Allows clearing the trip event log (trip cause, fault current value and operating time).
○
3
Alarm event log
Allows clearing the alarm event log (alarm cause, fault current value and operating time).
○
4
Max. demanded power
Allows clearing the max. demanded power (see Fig. 51
○
17
)
○
5
Max. phase current
Allows clearing the max. phase current (see Fig. 51
○
9
).
○
6
Integrated demand
Allows clearing the integrated demand.
○
7
Clear mode "Start"
Press ENTER to enter this subscreen from a reset subscreen. "NO" will flash. To exit this subscreen, press the right or left
key of the cross button.
○
8
Clear mode "YES"
Press the up or down key of the cross button. "YES" will appear. To exit this subscreen without clearing the item, press the
right or left key of the cross button.
○
9
Clear mode "Clear"
This subscreen appears when ENTER is pressed while "YES" is appearing. "SURE" will flash. To clear the item, press SET.
The subscreen will exit to the Setting 1 screen. To exit this subscreen without clearing the item, press the right or left key of
the cross button.
○
10
(Setting 1 screen)
See 5-3-2-6.
◯
1
◯
10
× 3
◯
2
◯
3
◯
4
◯
5
◯
6
Cancel
Clear
◯
7
◯
8
◯
9