7. TROUBLESHOOTING FLOWCHARTS
Figs. 99 - 103 are troubleshooting flowcharts where typical troubles and remedial actions are shown.
Fig. 99 Remedial actions against a system alarm(AGR-21B/22B/31B)
Fig. 100 Remedial actions against a symptom of "charging impossible"
Closing springs
cannot be charged
Is manual charging
possible?
Yes
Check the operation voltage.
OK
Check
the control circuit
and terminals. See Nos. 5
and 11 in Table
42.
OK
No
NG
NG
Contact Terasaki.
OK
Check the charging
mechanism. See No. 12
in Table 42.
Supply correct voltage.
Repair
NG
Repair
Is motor charging
possible?
No
Contact Terasaki.
Yes
Contact Terasaki.
No
Is manual charging
possible?
Yes
End
System alarm occurs
Is "SYS2" indicated?
No
Is "SYS1" indicated?
Yes
Yes
Check operating mechanism
See No. 12 in Table 42.
Normal
Check control circuit and MHT.
See No. 11 in Table 42 and Nos.
19
– 23 in Table 43.
Normal
Check ACB tripping operation.
See No. 27 in Table 43.
Normal
Does system alarm persist?
No
End
Abnormal
Abnormal
Abnormal
Yes
Remove cause.
Remove cause.
Contact Terasaki.