7.2.3.2.
Digital inputs
For every digital input, a description, up to 15 symbols and states up to 15 symbols can be set.
These descriptions will appear in the monitoring page, conditions page, XML/JSON data, SMS,
and e-mail alerts.
7.2.3.3.
Analog inputs
For every analog input, a description, up to 15 symbols can be set. These descriptions will
appear in the monitoring page, conditions page, XML/JSON data, SMS, and e-mail alerts.
For every analog input, fields “Unit”, “Multiplier” and “Offset” are available to convert the raw
voltage/current into meaningful engineering units. The scaled value is calculated by:
SV[Un] = RV * MU + OF
Where:
SV
–
scaled (displayed) value;
Un
–
unit;
RV
–
raw voltage from the source;
MU
–
multiplier;
OF
–
offset.
Example:
For humidity sensor HIH-4000-003 following data (from the datasheet) is available:
VOUT = 0.826
at 0% RH
VOUT = 3.198
at 75.3% RH
The raw values are voltages on the sensor’s output. Actually, we need to know relative
humidity (scaled value) not voltages. The two relations are enough to calculate multiplier