Ambient Relative Humidity: 5 to 85% (non-condensing)
•
Standards and Certifications
Safety: EN 62368-1:2014 + EN 62368-1:2014/AC1-3:2015 + EN 62368-1:2014/A11:2017 +
EN 62368-1:2014/AC:2017-03:2017, EN 62311:2008
EMC:
EN 55032: 2015 + EN 55032: 2015/AC:2016-07 + EN 55032: 2015/A11:2020
EN 55024: 2010 + EN 55024: 2010/A1:2015
EN 61000-3-2: 2014
EN 61000-3-3: 2013 + EN 61000-3-3: 2013/A1:2019
RFU:
EN 301 489-19 V2.1.1, EN 301511 V12.5.1, EN 301 908-1 V11.1.1,
EN 301 908-13 V11.1.2, EN 301 908-2 V11.1.2, EN 303 413 V1.1.1
Green: RoHS
•
Warranty
Warranty period: 3 years
•
Power supply
Operating voltage range (including -15/+20% according to IEC 62368-1): 10 to 28 VDC
Current consumption: 0.24A @ 12VDC
•
Cellular interface
Standards: LTE-FDD, EDGE and GPRS
TCG120-4E (hv2) bands:
4G LTE:
B1/B3/B5/B7/B8/B20
2G:
B3/B8
SIM card size: Standard
Antenna connector: SMA-F
•
Analog inputs
Isolation: Non-isolated
Type: Single-ended
Resolution: 10 bits
Input Range: 0 to 60 VDC
Accuracy: ±1%
Sampling Rate: 500ms per channel (averaged value of 250 samples)
Input Impedance: 1 mega-ohm (min.)
•
Digital inputs
Isolation: Non-isolated
Type: Dry contact and logic level
Minimum high-level input voltage for digital inputs: +2.5VDC
Maximum low-level input voltage for digital inputs: +0.8VDC
Maximum input voltage for digital inputs: +5.5VDC
Sampling rate: 10ms
Digital filtering time period: 30ms
•
Relay outputs
Type: Form C (N.O. and N.C. contacts)
Contact current rating: 3 A @ 24 VDC, 30 VAC (resistive load)