56050801 - Rev B
12
© 2017 Telguard
Step 5: Connect and Test the Trip Input (optional)
The trip input is connected to the external relay by wiring the external relay to
the TRIP IN terminal (pin 6) of the terminal block, and the other side to either
the TRIP GND terminal of the same block (pin 5) or to the chassis ground on the
Telguard circuit board.
Note that trip inputs are normally wired such that there is a 2.2kΩ resistor in
parallel with the external relay, so that a tamper condition (i.e. a cut wire) can
be detected.
When the trip input functionality is being used, closing the trip contact will
cause the Telguard to send a message to the TCC, which in turn will cause the TCC
to send a message to the central station. If the Telguard is configured to report
restorals, the contact opening will also be reported.
Step 6:
Complete the Telguard Installation
The last step is to permanently mount the Telguard.
1.
Attach earth ground to the grounding screw located on lower right-hand corner
of printed circuit board assembly and permanently mount the Telguard enclosure.
2.
Install mounting screws.
3.
Slide the enclosure onto these screws.
4.
Close the enclosure door and lock it