Sensor1SensorStatusHL
High level status of sensor.
bit0: Sensor enabled
bit1: Alarm 1 trip
bit2: Alarm 2 trip
bit3: Alarm 3 trip
bit4: Sensor fault
bit5: Sensor inhibited
bit6: Sensor connected
bit7: Sensor calibrating
bit8: Sensor Cal due
bit9: Loop signaling (0=live, 1=fixed)
bit10: Spare
bit11: Spare
bit12: Spare
bit13: Spare
bit 14, 15: Reserved
INT16U 2
Normal
Alarm
40135 86
R
Sensor2SensorStatusHL
INT16U 2
Normal
Alarm
40136 87
R
Sensor3SensorStatusHL
INT16U 2
Normal
Alarm
40137 88
R
Sensor1GasConc10Bit
200 = 0%Full Scale, 1000 = 100% Full Scale, 0
= -25%Full Scale
INT16U 2
RD
40138 89
R
Sensor2GasConc10Bit
INT16U 2
RD
40139 8A
R
Sensor3GasConc10Bit
INT16U 2
RD