MERIDIAN
UNIVERSAL GAS DETECTOR
CONFIGURATION & SETUP
5-29
USE AND DISCLOSURE OF DATA
Information contained herein is classified as EAR99 under the U.S. Export Administration Regulations. Export, reexport or diversion contrary to U.S. law is
prohibited.
Transmitter, cont.
Current Loops – 20mA Offset
0
Current Loops – Inhibit
17.38mA
Time/Date
Set/Confirm
Editor
Edit name, Lat or Long
Sensor
Range
0 to 25% is used in this example.
Note: Another range of 0 to 10% is
selectable.
Dead Band
0
Display Negative
No
Warm Up (SECS, MINS, HRS)
1M
Gas Type
Oxygen
Gas Units
%
Alarm Set 1
19.5% (default)
Alarm Reset 1
20.5% (default)
Alarm Set 2
16.0% (default)
Alarm Reset 2
17.0% (default)
Alarm Set 3
22.5.0% (default)
Alarm Reset 3
21.0% (default)
Editor – Name
Enter unique name
Editor – Gas 1
Enter unique name
Editor – Gas 2
Enter unique name
MODBUS
Address
1
Baud Rate
9600
Parity
None
Stop Bit
1
Application
Sensor Technology
E-Chem
Gas to Detect
O
2
(Oxygen)
Stop Bit
1
Table 5-12: Toxic (E-Chem) Example — O
2
(Continued)
Category
Item
Selection