4220 Flow Meter
Section 2 Programming
2-18
Programming for the conditions and values that determine the
operation of the 4-20 mA loop (or loops) is done in Programming
Step 2, following the entry of FLOW RATE AT MAXIMUM
HEAD.
Note
The information in the following section is provided for those
who can write their own software programs to process the data
transmitted from the Serial Output port. Special cables may be
required. Contact Teledyne Isco technical support for more
information.
Serial Output –
Returning to the OPTIONAL OUTPUTS menu,
you will see the SERIAL OUTPUt option. This feature lets the
flow meter transmit the most recent values for all currently
enabled ports as ASCII text. You can then write a simple
program to retrieve this data periodically, or you can do it inter-
actively using a terminal program.
Command Line:
(Use the INTERROGATOR connector.) The
lines of text contain the port values for each port that is turned
on. The DATA command will use a special command response
protocol. The following table provides the ASCII codes for port
types and standard units of measure.
Table 2-1 ASCII Output Codes
Code Parameter
Units
DE
Description
String
ID
Unit specific identifier
Unsigned long
MO
Model
String
TI
Time since 1900
Days
BV
Battery Voltage
Volts
LE
Level
Meters
LSI
Level Signal Strength
0 - 100%
FL
Flow
Cubic meters per second
VO
Volume
Cubic meters
FV
Forward volume
Cubic meters
RV
Reverse volume
Cubic meters
SV
Sampler Enabled Volume
Cubic Meters
RA
Rain (rolls over every 255 tips) Tips
CR
Current day’s rain (tips since
midnight)
Tips
PR
Previous day’s rain (tips since
midnight)
Tips
PH
pH
pH units
DO
Dissolved Oxygen
Milligrams per liter
TE
Temperature
Degrees Celsius
YPH
YSI 600 pH
pH units
YDO
YSI Dissolved Oxygen
Milligrams per liters
Summary of Contents for 4220
Page 2: ......
Page 4: ......
Page 8: ...4220 Flow Meter Safety ...
Page 14: ...vi ...
Page 19: ...4220 Flow Meter Section 1 Introduction 1 5 Figure 1 2 4220 Controls and Indicators ...
Page 28: ...4220 Flow Meter Section 1 Introduction 1 14 ...
Page 94: ...4220 Flow Meter Section 3 Installation 3 12 ...
Page 156: ...4220 Flow Meter Appendix A Replacement Parts A 2 ...
Page 157: ...4220 Flow Meter Appendix A Replacement Parts A 3 ...
Page 160: ...4220 Flow Meter Appendix A Replacement Parts A 6 ...
Page 164: ...4220 Flow Meter Appendix B Accessories List B 4 ...
Page 172: ...4220 Flow Meter Appendix C Programming Worksheets C 8 ...
Page 182: ...4220 Flow Meter Appendix D General Safety Procedures D 10 ...
Page 194: ......
Page 196: ...Warranty ...
Page 198: ......