Subject to modifications and errors
Page 55 of 71
2019-06-26 edition
ID
Default
Min
Max
Min
Max
.023
ULN<1 OFF
U
THR
OFF
%Unom
84
84
84
10
100
.024
ULN<1 ON
U
THR
ON
%Unom
86
86
100
10
100
.025
ULN<1 T
Time OFF
ms
10000
600
10000
200
60000
Only active for:
Connection Modes: 2-wire, 4-wire (LN), 4-wire (LN+LL))
Overvoltage2 Line to Line
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.027
ULL>2 OFF
U
THR
OFF
%Unom
121
121
121
100
135
.028
ULL>2 ON
U
THR
ON
%Unom
119
100
119
100
135
.029
ULL>2 T
Time OFF
ms
160
110
160
110
60000
Only active for:
Connection Modes: 3-wire, 4-wire (LN+LL)
Undervoltage2 Line to Line
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.031
ULL<2 OFF
U
THR
OFF
%Unom
49
49
49
10
100
.032
ULL<2 ON
U
THR
ON
%Unom
51
51
100
10
100
.033
ULL<2 T
Time OFF
ms
200
150
200
150
60000
Only active for:
Connection Modes: 3-wire, 4-wire (LN+LL)
Overvoltage2 Line to Neutral
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.035
ULN>2 OFF
U
THR
OFF
%Unom
121
121
121
100
135
.036
ULN>2 ON
U
THR
ON
%Unom
119
100
119
100
135
.037
ULN>2 T
Time OFF
ms
160
110
160
110
60000
Only active for:
Connection Modes: 2-wire, 4-wire (LN), 4-wire (LN+LL)
Undervoltage2 Line to Neutral
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.039
ULN<2 OFF
U
THR
OFF
%Unom
49
49
49
10
100
.040
ULN<2 ON
U
THR
ON
%Unom
51
51
100
10
100
.041
ULN<2 T
Time OFF
ms
200
150
200
150
60000
Only active for:
Connection Modes: 2-wire, 4-wire (LN), 4-wire (LN+LL)
Overerfrequency1
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.055
f>1 OFF
f
THR
OFF
Hz
52.00
52.00
52.00
50.00
60.00
.056
f>1 ON
f
THR
ON
Hz
50.50
50.00
50.50
50.00
60.00
.057
f>1 T
Time OFF
ms
4000
4000
4000
200
60000
Underfrequency1
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.059
f<1 OFF
f
THR
OFF
Hz
47.00
47.00
47.00
40.00
50.00
.060
f<1 ON
f
THR
ON
Hz
47.10
47.10
50.00
40.00
50.00
.061
f<1 T
Time OFF
ms
200
200
200
200
60000
Random over frequency
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.086
f>RND
Enable function
off
on … off
on … off
.087
f>RND OFF
f
THR
OFF
Hz
50.50
52.00
50.50
52.00
.088
f>RND ON
f
THR
ON
Hz
50.05
50.00
52.00
50.00
52.00
.089
f>RND T
Time OFF
ms
4000
4000
4000
50
60000
Comment:
The random f
THR
OFF threshold is shown in .087 and cannot be edited
Rate of Change of Frequency (RoCoF)
Conformity Range
Possible Range